HVAC Mode — TEMPERING HICOOL (12) — The econ-

omizer is at minimum vent position but the combination of the

outside-air temperature and the economizer position has

dropped the supply-air temperature below the tempering cool

set point. Staged gas heat is used to temper the ventilation air.
HVAC Mode — VENT (13) — This is a normal operation

mode where no heating or cooling is required and outside air is

being delivered to the space to control IAQ levels.
HVAC Mode — LOW COOL (14) — This is a normal cool-

ing mode where a low cooling demand is required.
HVAC Mode — HIGH COOL (15) — This is a normal cool-

ing mode where a high cooling demand is required.
HVAC Mode — LOW HEAT (16) — The unit will be in low

heating demand mode using either gas or electric heat.
HVAC Mode — HIGH HEAT (17) — The unit will be in

high heating demand mode using either gas or electric heat.
HVAC Mode — UNOCC. FREE COOL (18) — In this

mode the unit will operate in cooling but will be using the

economizer for free cooling. Entering this mode will depend on

the status of the outside air. The unit can be configured for out-

side air changeover, differential dry bulb changeover, outside

air enthalpy changeover, differential enthalpy changeover, or a

custom arrangement of enthalpy/dewpoint and dry bulb. See

the Economizer section for further details.
HVAC Mode — FIRE SHUT DOWN (19) — The unit has

been stopped due to a fire shutdown input (FSD) or two or

more of the fire control modes, purge, evacuation, or pressur-

ization have been requested simultaneously.
HVAC Mode — PRESSURIZATION (20) — The unit is in

the special fire pressurization mode where the supply fan is on,

the economizer damper is open and the power exhaust fans are

off. This mode is started by the Fire Pressurization (PRES) in-

put which can be found in the INPUT

FIRE sub-menu.

HVAC Mode — EVACUATION (21) — The unit is in the

special Fire Evacuation mode where the supply fan is off, the

economizer damper is closed and the power exhaust fans are

on. This mode is started by the Fire Evacuation (EVAC) input

which can be found in the INPUT

FIRE sub-menu.

HVAC Mode — SMOKE PURGE (22) — The unit is in the

special Fire Purge mode where the supply fan is on, the econo-

mizer damper is open and the power exhaust fans are on. This

mode is started by the Fire Evacuation (PURG) input which

can be found in the INPUT

FIRE sub-menu.

HVAC Mode — DEHUMIDIFICATION (23) — The unit is

operating in Dehumidification mode.
HVAC Mode — REHEAT (24) — The unit is operating in

reheat mode.

Unit Configuration Submenu —

The UNIT sub-

menu under the Configuration mode of the local display

contains general unit configuration items. The sub-menu which

contains these configurations is located at the local display un-

der Configuration

UNIT. See Table 43.

Machine Control Type (C.TYP) — This configuration de-

fines the control type and control source responsible for select-

ing a cooling, heating, or vent mode and in determining the

method by which compressors are staged. The control types

are:
C.TYP = 1 (VAV-RAT) and C.TYP = 2 (VAV-SPT)

Both of these configurations refer to standard VAV opera-

tion. If the control is occupied, the supply fan is run

continuously and return-air temperature will be used in the

determination of the selection of a cooling mode. VAV-SPT

differs from VAV-RAT only in that during the unoccupied

period, space temperature will be used instead of return-air

temperature to start the fan for 10 minutes to establish an

accurate return-air temperature before the return-air temper-

ature is allowed to call out any mode.

C.TYP = 3 (TSTAT-MULTI)

This configuration will force the control to monitor the ther-

mostat inputs to make a determination of mode. Unlike

traditional 2-stage thermostat control, the unit is allowed to

use multiple stages of cooling control and perform VAV-

type operation. The control will be able to call out a LOW

COOL or a HIGH COOL mode and maintain a low or high

cool supply air set point.

C.TYP = 4 (TSTAT-2 STG)

This configuration will force the control to monitor the ther-

mostat inputs to make a determination of mode and allow

only 2 stages of control for both heating and cooling.

C.TYP = 5 (SPT-MULTI)

This configuration will force the control to monitor a space

temperature sensor to make a determination of mode.

Unlike traditional 2-stage space temperature control, the

unit is allowed to use multiple stages of cooling control and

perform VAV-type operation. The control will be able to call

out a LOW COOL or a HIGH COOL mode and maintain a

low or high cool supply air set point.

C.TYP = 6 (SPT-2 STG)

This configuration will force the control to monitor the

space temperature sensor to make a determination of mode

and allow 2 stages of control for both heating and cooling.

FAN MODE (CV.FN) — The Fan Mode configuration can be

used for machine control types (Configuration

UNIT

C.TYP) 3, 4, 5, and 6. The Fan Mode variable

establishes the operating sequence for the supply fan during

occupied periods. When set to 1 (Continuous), the fan will

operate continuously during occupied periods. When set to 0

(Automatic), the fan will run only during a heating or cooling

mode.
REMOTE SWITCH CONFIG (RM.CF) — The remote switch

input is connected to TB6 terminals 1 and 3. This switch can be

used for several remote control functions. Please refer to the

Remote Control Switch Input section for details on its use and

operation.
CEM MODEL INSTALLED (CEM) — This configuration in-

structs the control to communicate with the controls expansion

module (CEM) over the Local Equipment Network (LEN) when

set to Yes. When the unit is configured for certain sensors and

configurations, this option will be set to Yes automatically.

The sensors and configurations that automatically turn on

this board are:
Configuration

UNIT

SFS.M = 1 (Supply Fan Status

Switch Monitoring)
Configuration

EDT.R

RES.S = Enable (4 to 20 mA Sup-

ply Air Reset Sensor Enable)
Configuration

DMD.L

DM.L.S = 1 (2 SWITCHES)

(Demand Limiting using 2 discrete switches)
Configuration

DMD.L

DM.L.S = 2 (4-20 MA CTRL)

(Demand Limiting using a 4 to 20 mA sensor)
Configuration

IAQ

AQ.CF

IQ.I.C = 1 (IAQ DISCRETE)

(IAQ discrete switch control)
Configuration

IAQ

AQ.CF

IQ.I.C = 2 (IAQ DISC.OVR)

(IAQ discrete switch “override” control)
Configuration

IAQ

AQ.CF

OQ.A.C = 1 (OAQ SENS-

DAQ) (Outdoor Air Quality Sensor)
Configuration

IAQ

AQ.CF

OQ.A.C = 2 (4-20 NO

DAQ) (4 to 20 mA sensor, no DAQ)
Temperature Compensated Start Cooling Factor (TCS.C) —

This factor is used in the equation of the Temperature Compen-

sated Start Time Bias for cooling. Refer to the Temperature