CONSTANT VOLUME 2-STAGE CONTROL (BP.CF = 1)

OPERATION — Two exhaust fan relays will be turned on and

off based on economizer position. The two trip set points are

BP.P1 and BP.P2. If the economizer is greater than or equal

to BP.P1, then power exhaust stage 1 is requested and a

60-second timer is initialized. If the economizer is 5% below

the BP.P1, then power exhaust stage 1 is turned off. Also, if the

economizer position is less than BP.P1 and the 60-second timer

has expired, power exhaust stage 1 is turned off. The same

logic applies to the second power exhaust stage, except the

BP.P2 trip point is monitored. If the economizer position is

greater than or equal to BP.P2, then power exhaust stage 2

is energized and a 60-second timer is initialized. If the econo-

mizer is 5% below the BP.P2 the second power exhaust

stage turned off. If the economizer is less than BP.P2 and the

60-second timer has expired, second stage power exhaust is

turned off.

For BP.CF=1, the Table 82 illustrates the power exhaust

stages 1 and 2, relay combinations based upon Configuration

BP.MT (4 or 6 motors).

MULTIPLE POWER EXHAUST STAGE BUILDING

PRESSURE CONTROL (BP.CF = 2) OPERATION —

Building pressure control is active whenever the supply fan is

running. The control algorithm to be used (BP.SL=1) is a timed

threshold technique for bringing stages of power exhaust on

and off.

The number of power exhaust stages available for this con-

trol algorithm is a function of the number of motors it supports.

This number of motors is defined by the Configuration

BP

BP.MT configuration. Table 83 illustrates the staging tables

for this control algorithm based on BP.MT.

The following configurations are used in the controlling of

building pressure with this algorithm:
Configuration

BP

B.CFG

BP.HP (building pressure

high threshold level)

Configuration

BP

B.CFG

BP.LP (building pressure

low threshold level)

Configuration

BP

B.CFG

BP.TM (building pressure

timer)
This control function is allowed to add or select power ex-

haust stages at any time, except that a delay time must expire

after a stage is added or subtracted. Any time a stage change is

made, a timer is started which delays staging for 10 * BP.TM

seconds. The default for BP.TM is 1, therefore the delay

between stage changes is set to 10 seconds.

The logic to add or subtract a stage of power exhaust is as

follows:
• If building pressure (Pressures

AIR.P

BP) is greater

than the building pressure set point (Configuration

BP

BPSP) plus the building pressure high threshold level

(Configuration

BP

B.CFG

BP.HP) add a stage of

power exhaust.

Table 81 — Building Pressure Configuration

*Some configurations are machine dependent.

Table 82 — Power Exhaust Staging (BP.CF = 1)

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

BP

BUILDING PRESS. CONFIG

BP.CF

Building Press. Config

0-3

BLDG_CFG

0*



BP.RT

Bldg.Pres.PID Run Rate

5-120

sec

BPIDRATE

10



BP.P

Bldg. Press. Prop. Gain

0-5

BLDGP_PG

0.5



BP.I

Bldg.Press.Integ.Gain

0-2

BLDGP_IG

0.5



BP.D

Bldg.Press.Deriv.Gain

0-5

BLDGP_DG

0.3



BP.SO

BP Setpoint Offset

0.0 - 0.5

"H2O

BPSO

0.05



BP.MN

BP VFD Minimum Speed

0-100

%

BLDGPMIN

10



BP.MX

BP VFD Maximum Speed

0-100

%

BLDGPMAX

100



BP.FS

VFD/Act. Fire Speed/Pos.

0-100

%

BLDGPFSO

100

BP.MT

Power Exhaust Motors

1-2

PWRM

1*

BP.S

Building Pressure Sensor

Enable/Dsable

BPSENS

Dsable*

BP.R

Bldg Press (+/–) Range

0 - 1.00

"H2O

BP_RANGE

0.25

BP.SP

Building Pressure Setp.

-0.25 -> 0.25

"H2O

BPSP

0.05

BP.P1

Power Exhaust On Setp.1

0 - 100

%

PES1

35

BP.P2

Power Exhaust On Setp.2

0 - 100

%

PES2

75

B.CFG

BP ALGORITHM CONFIGS

BP.SL

Modulating PE Alg. Slct.

1-3

BPSELECT

1

BP.TM

BP PID Evaluation Time

0 - 10

min

BPPERIOD

1

BP.ZG

BP Threshold Adjustment

0.1 - 10.0

"H2O

BPZ_GAIN

1

BP.HP

High BP Level

0 - 1.000

"H2O

BPHPLVL

0.05

BP.LP

Low BP Level

0 - 1.000

"H2O

BPLPLVL

0.04

BP.MT = 1 (4 motors)

PE.A

PE.B

PE.C

Power Exhaust Stage 0

OFF

OFF

OFF

Power Exhaust Stage 1

OFF

ON

OFF

Power Exhaust Stage 2

ON

ON

ON

BP.MT = 2 (6 motors)

PE.A

PE.B

PE.C

Power Exhaust Stage 0

OFF

OFF

OFF

Power Exhaust Stage 1

OFF

OFF

ON

Power Exhaust Stage 2

ON

ON

ON