Table 107 — Cooling Information Display Table
Table 108 — Mode Trip Helper Display Table
Table 109 — CCN/Linkage Display Table
Table 110 — Compressor Run Hours Display Table
Table 111 — Compressor Starts Display Table
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
COOL
COOLING INFORMATION
C.CAP
Current Running Capacity
%
CAPTOTAL
CUR.S
Current Cool Stage
COOL_STG
REQ.S
Requested Cool Stage
CL_STAGE
MAX.S
Maximum Cool Stages
CLMAXSTG
DEM.L
Active Demand Limit
%
DEM_LIM
forcible
SUMZ
COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor
–100
+100
SMZ
ADD.R
Next Stage EDT Decrease
^F
ADDRISE
SUB.R
Next Stage EDT Increase
^F
SUBRISE
R.PCT
Rise Per Percent Capacity
RISE_PCT
Y.MIN
Cap Deadband Subtracting
Y_MINUS
Y.PLU
Cap Deadband Adding
Y_PLUS
Z.MIN
Cap Threshold Subtracting
Z_MINUS
Z.PLU
Cap Threshold Adding
Z_PLUS
H.TMP
High Temp Cap Override
HI_TEMP
L.TMP
Low Temp Cap Override
LOW_TEMP
PULL
Pull Down Cap Override
PULLDOWN
SLOW
Slow Change Cap Override
SLO_CHNG
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
TRIP
MODE TRIP HELPER
UN.C.S
Unoccup. Cool Mode Start
UCCLSTRT
UN.C.E
Unoccup. Cool Mode End
UCCL_END
OC.C.S
Occupied Cool Mode Start
OCCLSTRT
OC.C.E
Occupied Cool Mode End
OCCL_END
TEMP
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
OC.H.E
Occupied Heat Mode End
OCHT_END
OC.H.S
Occupied Heat Mode Start
OCHTSTRT
UN.H.E
Unoccup. Heat Mode End
UCHT_END
UN.H.S
Unoccup. Heat Mode Start
UCHTSTRT
HVAC
ascii string spelling out the hvac modes
string
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
LINK
CCN - LINKAGE
MODE
Linkage Active - CCN
ON/OFF
MODELINK
L.Z.T
Linkage Zone Control Tmp
dF
LZT
L.C.SP
Linkage Curr. Cool Setpt
dF
LCSP
L.H.SP
Linkage Curr. Heat Setpt
dF
LHSP
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
HRS
COMPRESSOR RUN HOURS
HR.A1
Compressor A1 Run Hours
0-999999
HRS
HR_A1
config
HR.A2
Compressor A2 Run Hours
0-999999
HRS
HR_A2
config
HR.B1
Compressor B1 Run Hours
0-999999
HRS
HR_B1
config
HR.B2
Compressor B2 Run Hours
0-999999
HRS
HR_B2
config
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
STRT
COMPRESSOR STARTS
ST.A1
Compressor A1 Starts
0-999999
CY_A1
config
ST.A2
Compressor A2 Starts
0-999999
CY_A2
config
ST.B1
Compressor B1 Starts
0-999999
CY_B1
config
ST.B2
Compressor B2 Starts
0-999999
CY_B2
config