CONTROLS SET POINT AND CONFIGURATION LOG

MODEL NUMBER:

Software Version

SERIAL NUMBER:

MBB

CESR131343--

DATE:

RCB

CESR131249--

TECHNICIAN:

ECB

CESR131249--

NAVI

CESR131227--

SCB

CESR131226--

CEM

CESR131174--

MARQ

CESR131171--

ITEM

EXPANSION

RANGE

DEFAULT

ENTRY

UNIT

UNIT CONFIGURATION

C.TYP

Machine Control Type

1 - 6 (multi-text strings)

4

CV.FN

Fan Mode (0=Auto, 1=Cont)

0 - 1 (multi-text strings)

1

RM.CF

Remote Switch Config

0 - 3 (multi-text strings)

0

CEM

CEM Module Installed

Yes/No

No

TCS.C

Temp.Cmp.Strt.Cool Factr

0 - 60 min

0

TCS.H

Temp.Cmp.Strt.Heat Factr

0 - 60 min

0

SFS.S

Fan Fail Shuts Down Unit

Yes/No

No

SFS.M

Fan Stat Monitoring Type

0 - 2 (multi-text strings)

0

VAV.S

VAV Unocc.Fan Retry Time

0 - 720 min

50

SIZE

Unit Size (20-60)

20 - 60

20

DP.XR

Disch.Press. Transducers

Yes/No

No

SP.XR

Suct. Pres. Trans. Type

0 -1 (multi-text strings)

0

RFG.T

Refrig: 0=R22 1=R410A

0 -1 (multi-text strings)

1

CND.T

Cnd HX Typ:0=RTPF 1=MCHX

0 -1 (multi-text strings)

0

MAT.S

MAT Calc Config

0 - 2 (multi-text strings)

1

MAT.R

Reset MAT Table Entries?

Yes/No

No

MAT.D

MAT Outside Air Default

0-100%

20

ALTI

Altitude……..in feet:

0 - 60000

0

DLAY

Startup Delay Time

0 - 900 sec

0

STAT

TSTAT_Both Heat and Cool

Yes/No

No

AUX.R

Auxiliary Relay Config

0 - 3

0

SENS

INPUT SENSOR CONFIG

SENS

SPT.S

Space Temp Sensor

Enable/Disable

Disable

SENS

SP.O.S

Space Temp Offset Sensor

Enable/Disable

Disable

SENS

SP.O.R

Space Temp Offset Range

1 - 10

5

SENS

RRH.S

Return Air RH Sensor

Enable/Disable

Disable

SENS

FLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

Disable

COOL

COOLING CONFIGURATION

Z.GN

Capacity Threshold Adjst

–10

- 10

1

MC.LO

Compressor Lockout Temp

–20 - 55 dF

40

C.FOD

Fan-Off Delay, Mech Cool

0 - 600 sec

60

MLV

Min. Load Valve? (HGBP)

Yes/No

No

M.M.

Motor Master Control

Yes/No

No

HPSP

Head Pressure Setpoint

80 - 150 dF

113

A1.EN

Enable Compressor A1

Enable/Disable

Enable

A2.EN

Enable Compressor A2

Enable/Disable

Enable

B1.EN

Enable Compressor B1

Enable/Disable

Enable

B2.EN

Enable Compressor B2

Enable/Disable

Enable

CS.A1

CSB A1 Feedback Alarm

Enable/Disable

Enable

CS.A2

CSB A2 Feedback Alarm

Enable/Disable

Enable

CS.B1

CSB B1 Feedback Alarm

Enable/Disable

Enable

CS.B2

CSB B2 Feedback Alarm

Enable/Disable

Enable

REV.R

Rev Rotation Verified ?

Yes/No

No

H.SST

Hi SST Alert DelayTime

5 - 30 min

10

EDT.R

EVAP.DISCHRGE TEMP RESET

RS.CF

EDT Reset Configuration

0 - 3 (multi-text strings)

0

RTIO

Reset Ratio

0 - 10

2

LIMT

Reset Limit

0 - 20 ^F

10

RES.S

EDT 4-20 ma Reset Input

Enable/Disable

Disable

Advertising