182

APPENDIX E — UPC OPEN CONTROLLER (cont)

NETWORK POINTS LIST (cont)

LEGEND

BACNET

OBJECT ID

POINT NAME

READ

ONLY

UNITS

DEFAULT

VALUE

RANGE

BACNET

OBJECT NAME

UNIT

POINT

BV:1052

Filter Status Input

W

n/a

n/a

0-1

filter_status_1

FLTS

BV:1060

Evacuation Input

W

n/a

n/a

0-1

smk_evac_1

EVAC

BV:1061

Pressurization Input

W

n/a

n/a

0-1

smk_press_1

PRES

BV:1062

Smoke Purge Input

W

n/a

n/a

0-1

smk_purg_1

PURG

BV:2001

Supply Fan State

R

n/a

n/a

n/a

sfan_1

SFAN

BV:2004

Supply Fan Request

W

n/a

n/a

0-1

sfan_forc_1

SFANFORC

BV:2008

Occupied?

W

n/a

n/a

0-1

occ_status_1

OCCUPIED

BV:2012

Condenser Fan Circuit A

R

n/a

n/a

n/a

cond_fan_a_1

CONDFANA

BV:2013

Condenser Fan Circuit B

R

n/a

n/a

n/a

cond_fan_b_1

CONDFANB

BV:2014

Remote Alarm/Aux Relay

W

n/a

n/a

0-1

aux_relay_1

ALRM

BV:2911

User Defined Binary 1

n/a

n/a

n/a

n/a

user_binary_1_1

n/a

BV:2912

User Defined Binary 2

n/a

n/a

n/a

n/a

user_binary_2_1

n/a

BV:2913

User Defined Binary 3

n/a

n/a

n/a

n/a

user_binary_3_1

n/a

BV:2914

User Defined Binary 4

n/a

n/a

n/a

n/a

user_binary_4_1

n/a

BV:2915

User Defined Binary 5

n/a

n/a

n/a

n/a

user_binary_5_1

n/a

BV:2999

Element Comm Status

n/a

n/a

n/a

n/a

element_stat_1

n/a

BP

— Building Pressure

CEM

— Controls Expansion Module

DAQ

— Differential Air Quality

DBC

— Dry Bulb Changeover

DDBC

— Differential Dry Bulb Changeover

DEC

— Differential Enthalpy Changeover

DH

— Dehumidification

IAQ

— Indoor Air Quality

LAT

— Leaving Air Temperature

n/a

— Not Available

OAEC

— Outdoor Air Enthalpy Changeover

OAT

— Outdoor Air Temperature

PID

— Proportional, Integral, Derivative

R

— Read

RAT

— Return Air Temperature

RH

— Relative Humidity

SASP

— Supply Air Set Point

SPT

— Space Temperature

TSTAT

— Thermostat

VAV

— Variable Air Volume

VFD

— Variable Frequency Drive

W

— Write