24

Side Wall

Terminations

3" (80mm) Minimum horizontal

separation between combustion air

intake and vent terminations.

8" (203mm) Minimum vertical

separation between combustion air

intake and vent terminations.

12" (305mm) Separation between

bottom of combustion air intake and

bottom of vent.

Multiple terminations as shown

in 6-1, 6-2, and 6-3 must be

a minimum of 12” (305mm)

horizontally between vent of one

termination and air intake of next

appliance.

Maximum allowable total outside

exposure vent length equals 10 ft.

(3.05m).

Maintain a pitch of 1/2" per ft.

(42mm/m) outside exposure back to

boiler to ensure proper condensate

drainage for horizontal runs.

Roof

Terminations

3" (80mm) Minimum horizontal

separation between combustion air

intake and vent of same appliance.

8" (203mm) Minimum vertical

separation between combustion

air intake and vent of different

appliances.

15" (381mm) Maximum horizontal

length of vent.

Minimum vent/intake between

different appliances 12" (305mm).

Maximum allowable total vertical

vent length with outside exposure is

10 ft.(3.05m).

Abandoned unused masonry

chimney may be used as chaseway

for combustion air and vent. Both

combustion air and vent pipe must

exit above top of chimney with

clearances as shown in figure 6-1.

12" (305mm)

Minimum

8" (203mm)

Minimum

15" (381mm)

Maximum

3" (80mm)

Minimum

Vent

Combustion

Air

12" (305mm) US,

18" (458mm) Canada

Minimum Above

Anticipated Snow Line

Vent

3" (80mm)

Minimum

Separation

12" (305mm)

Minimum From

Overhang

12" (305mm) Separation

Between Bottom Of

Combustion Air Intake And

Bottom Of Vent

See Snow & Ice

Page 22

Combustion Air

Vent

12" (305mm)

Minimum

Separation

See snow & ice

page 23

FIGURE 6-1 Two Pipe Roof Vent

FIGURE 6-2 Two Pipe Side Wall Vent

FIGURE 6-3 Two Pipe Side Wall Vent (Multiple Appliances.

Combustion Air

Roof Line

6 - COMBUSTION AIR AND VENT PIPING