13 - TROUBLE SHOOTING

YES

Remo

ve all liquid

from connector

.

Check for leaks. Repair all leaks.

Replace Control Module

Replace R

eturn W

ater

Sensor

Is correct harness connected to return

sensor (2 Brown Wires)?

YES

NO

Correct wiring

Unplug molex connector on return sensor

. Is there moisture or liquid on

metal pins? Liquid might be w

ater or

antifreez

e solution.

NO

Is Heat Ex

changer Pump

properly oriented?

(Pump arrow pointing down?)

YES

NO

Disconnect harness from

Return W

ater Sensor

. Measure

resistance using digital ohm meter

. Is resistance between

950 to 33,000 ohms?

Install Heat

Ex

changer Pump in

proper orientation

YES

NO

Replace

Control

Module

Verify

order of

pins

on

J2.

Pin

order

should

be:

empty,

black (or red),

white,

green.

Measure volts

on

pins

of

black

wire a

nd

white wire.

Is

wiring/pins in

right order?

D

oes black/wire ha

ve 120

VAC? D

oes

white wire/pin have

0

VAC?