8.1 General

Electrically bond boiler to ground in accordance with

requirements of authority having jurisdiction. Refer to:

• USA- National Electrical Code, ANSI/NFPA 70.

8.2 Electric Knockouts (figure 8-1)

• Five knockouts located on bottom of chassis.

A. Three knockouts located under junction box are

reserved for high voltage wires. Choose connectors

using total diameter of wire bundles.

B. Two knockouts located to right of high voltage

knockouts (outside of junction box) are reserved

for low voltage wiring. Use supplied grommets

when using these knockouts.

8.3 Line Voltage Connections (figure 8-2)

• Boiler

A. Provide individual 120V, 15 amp circuit

(recommended) with fused disconnect or service

switch as required by authority having jurisdiction.

B. Open High Voltage Junction Box (see figures 3-4

and 3-5) to access line voltage terminal strip.

C. Connect 120 VAC circuit to line voltage terminal

strip 120 VAC L,N,G.

• Central Heating Pump, if used.

A. Isolate pump from control module if pump FLA (Full

Load Amps) exceeds maximum allowable current

draw. See Figure 8-3 and Table 11.

B. Connect pump to line voltage terminal strip CH

PUMP L,N,G.

• Domestic Hot Water Pump, if used.

A. Isolate pump from control module if pump FLA

exceeds maximum allowable current draw. See

Figure 8-3 and Table 11.

B. Connect pump to line voltage terminal strip DHW

PUMP L,N,G.

8.4 External Connections (figure 8-4)

• User Interface Terminals

A. Factory wired to USER INTERFACE terminals

B. Optional - Remote mount user interface for

improved access. Use low voltage knockout.

C. Maximum wire length is 100 ft (30m) for 22 ga.

wire, or 150 ft (45m) for 18 ga. wire.

• Argus Link (Multiple boiler applications only)

WARNING

Electrical shock hazard. Turn OFF electrical power

supply at service panel before making electrical

connections. Failure to do so could result in death

or serious injury.

!

FIGURE

8-2

Line Voltage Connections

NOTICE

Wiring diagrams can be found in Section 14 of this

Manual.

FIGURE

8-1

Electric Knockouts Bottom Of Boiler

4½"

(114mm)

5"

(127mm)

High Voltage

Knockouts

Low Voltage Knockouts

(Use supplied

grommets when using

these knockouts)

Front of Boiler

Back of Boiler

8 - ELECTRICAL CONNECTIONS

MBH

CH PUMP

DHW PUMP

NOTE

50

75

100

1 A

1 A

Powered by

Control Board

150

200

299

10 A

10 A

Powered by

installed 10 Amp

relay

If CH or DHW pump current is more than the maximum

allowable current draw install proper field sourced relays

as shown in figure 8-3.

Table 11 -

Maximum Allowable Current Draw