Ch settings – Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 79

Advertising
background image

79

User Interface Display

Explanation

CH Settings

4. Central Heating (CH) modes available:

• CH Mode = 0 ‘CH with Thermostat’

• Boiler will attempt to satisfy CH demand while CH

thermostat input is closed.

• Boiler will modulate its firing rate to maintain CH set

point and match system heat load.

• CH set point adjusted in ‘Settings’ submenu under ‘User

Menu’

• CH Mode = 1 ‘CH with Thermostat and Outdoor Reset’

• Boiler will attempt to satisfy CH demand when CH

thermostat input is closed.

• Boiler will modulate its firing rate to maintain CH set

point and match system heat load.

• CH set point calculated as function of outdoor

temperature using outdoor reset curve. See Figure A-2

• CH Mode = 2 ‘CH with Full Outdoor Reset’

• CH demand is determined by outdoor temperature and

Warm Weather Shutdown temperature.

• Boiler will permanently attempt to satisfy CH

demand, when CH demand is available.

• CH thermostat input is ignored.
• CH set point calculated as function of outdoor

temperature using outdoor reset curve. See Figure A-2

• CH Mode = 3 ‘CH with Permanent Demand’

• CH demand is prermanently on.
• Boiler will permanently attempt to satisfy CH

demand.

• CH thermostat input is ignored.
• CH set point is adjusted in ‘Settings’ submenu under

‘User Menu’

Note:
• Once CH demand is satisfied (i.e. CH thermostat opens or

boiler determines its minimum firing rate exceeds system

heating load):

• Burner shuts off, boiler enters post purge.
• CH pump continues to run for 30 seconds.
• Control will wait until Anti-cycle time of 180 seconds

elapses before boiler fires again. Prevents short-

cycling.

• The internal heat exchanger pump is energized anytime demand

exists regardless of Pump Mode setting or type of demand (CH or

DHW).