48

Screen Display

Explanation

Go to Page For

Troubleshooting

Control has blocking error for more than 20

hours in a row.

Go to Page 50

Three unsuccessful ignition attempts in a row

Go to Page 51

Open gas valve power circuit. May involve

high temperature switch, gas valve, or gas

valve relay in control module.

Go to Page 50

Safety Circuit is open.

Go to Page 52

Blower speed does not reach speed calculated

by Control Module.

Go to Page 53

Control Module internal error.

Replace Control

Module

High Temperature opens during normal

operation.

Go to Page 54

Control Module detects flame after gas valve

is closed more than 10 seconds.

Replace Gas Valve

Flame is detected before gas valve opens.

Replace Gas Valve

Control module internal error.

Replace Control

Module

Lost flame signal 3 times during one heat call.

Go to Page 55

Control Module internal error.

Replace Control

Module

Control Module internal error.

Replace Control

Module

External voltage supplied to DHW T-T or CH

T-T terminals. Eliminate voltage using dry

contact relay.

-

Flame detected when gas valve is closed.

Go to Page 55

B l o c k i n g E r r o r

R E F L O t o o L O

13 - TROUBLE SHOOTING