13 - TROUBLE SHOOTING

Error shows when safet

y circuit is

open. R

emo

ve J13 connector from

control module. Check for continuit

y

between two pins connected to two pink wires, is continuit

y a

vailable?

YES

NO

Replace Control Module

Boiler fired without enough w

ater flow

through heat ex

changer

. Heat ex

changer

is o

ver heated. Either high limit or heat

ex

changer temper

ature switch is open.

Check the following:

Air in system?

Verify water flow in system piping

Flush system if water is dirty.

Is boiler supply pipe (abo

ve

heat ex

changer) hot?

W

ait for boiler to cool down.

YES

NO

Replace Brok

en S

witch

Unplug molex connector on supply temper

ature sensor

. Check continuit

y

between two pins on sensor (two pins

connected

to

two

pink

wires)

.

Is continuit

y a

vailable?

YES

NO

Check for loose connections on two pink wires on J13 connector

, supply sensor

, and

safet

y temper

ature switch.

YES

NO

Fix Loose Connections

Replace Wire Harness

Let all z

ones

run until w

ater

temper

ature

drops.

Is Heat Ex

changer surface hot?

YES

NO

Check high limit

and surface temper

ature

switches