4 domestic hot water system design, 3 heating system design – Glow-worm 30ci Plus User Manual

Page 12

Advertising
background image

12

4000123944-2

• Copper tubing or plastic Hep

2

0 may be used for the domestic

hot water system. Unecessary pressure losses should be
avoided.

• Provision shall be made for a drain valve at the lowest points
of the system.

• The flow restrictor must be fitted limiting the flow through the
boiler to a maximum of 12 l/min.

• The boiler will operate with a minimum supply pressure of 0,5
bar, at reduced flow rate.

Best operating comfort will be obtained from a supply pressure
of 1 bar.

4.1 Hard Water Areas

In areas where the water is 'hard', more than 200mg/litre, it is
recommended that a proprietary scale reducer is fitted in the
cold water supply to the boiler.

4 Domestic Hot Water System Design

0

10

20

30

40

50

60

70

0

200

400

600

800

1000

1200

1400

Flow rate through heating system l/h

Available pressure (kPa)

between heating supply and return

1

2

3

4

5

11357

(10 kPa = 1 m WG)

1

2

3

4

5

Bypass fully shut

Open 1/4 turn

Open 1/2 turn

Open 1 turn

Open 2 turns

Diagram 3.1

Diagram 3.2

10015

Flow

control valve

Drain point

Bypass

valve

Domestic

water

Heating
circuit

Return

Additional
expansion
vessel
(if required)

Boiler

Hot

Cold supply

Filling device

Bypass
(If required)

*

*

'A'

3 Heating System Design

3.1 Bypass

•The boiler is fitted with an adjustable automatic bypass.
Ensure that under no circumstances does the flow rate drop
below the figure specified, see Table 1.

• A bypass is not required on the central heating circuit unless
the system controls could allow the boiler to operate when
there is no flow.

• Where a bypass has to be fitted, the bypass must be placed
at least 1.5 metres from the appliance, see diagram 3.2.

3.2 Filling the system

A filling device is fitted to the boiler to initially fill the system and
replace water lost during servicing, see the relevant parts of
diagram 2 controls and lighting and diagram 3.2.

TABLE 1. FLOW RATE

Model

Minimum flow rate

30ci plus

21.26 litres per minute

This is equal to 20

°

C differential at maximum heat input