4000123944-2

6 Boiler Location, Flue and Ventilation

Diagram 6.2

MINIMUM SITING DIMENSIONS FOR THE
POSITIONING OF FLUE TERMINALS

MM

HORIZONTAL FLUES
A

DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR BRICK,
OPENING WINDOWS, AIR VENT, OR ANY
OTHER VENTILATION OPENING

300

B

BELOW GUTTER, DRAIN/SOIL PIPE

75

C

BELOW EAVES

200

D

BELOW A BALCONY OR CAR PORT

200

E

FROM VERTICAL DRAIN PIPES AND
SOIL PIPES

150

F

FROM INTERNAL/EXTERNAL CORNERS

OR TO A BOUNDARY ALONGSIDE THE

TERMINAL

300

G

ABOVE ADJACENT GROUND OR
BALCONY LEVEL

300

H

FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL

600

I

FACING TERMINALS

1200

J

FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING

1200

K

VERTICAL FROM A TERMINAL

1500

L

HORIZONTALLY FROM A TERMINAL

300

VERTICAL FLUES
M

FROM ADJACENT WALL TO FLUE

300

N

FROM ANOTHER TERMINAL

600

P

FROM ADJACENT OPENING WINDOW

1000

Q

ABOVE ROOF LEVEL

300

11508

Diagram 6.3

6.2 Terminal guard, see diagram 6.3.

A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.

If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
to be central over the terminal.

A suitable terminal guard type K3 can be supplied by:

Tower flue components Ltd.
Morley road
Tonbridge
Kent
TN9 1RA

6.3 Flue options

There are various flue systems to choose from as follows:

Horizontal telescopic rear flue pack.

Horizontal telescopic top flue pack.

Horizontal top flue pack.

Horizontal extended flue pack.

Vertical flue pack.

Twin flue pack.

Extensions, 90

°

and 45

°

bends.

For detailed information refer to flue options guide. This is
available from your nearest stockist.

6.4 Cupboard or compartment ventilation

The boiler can be fitted in a cupboard or compartment without
the need for permanent ventilation.