18 Fault Finding

COMPONENT

NORMAL MEASURE

CHECK

Gas control valve

Under demand during ignition sparks:

If 0 Volt: the gas control valve

Resistance of coil 116

24V dc for 1 to 2 seconds, then

is not faulty.

12Vdc (constant) at the gas control

If 24 Volts and then 12 Volts

valve electrical connection.

but no gas at the burner:
Check if the gas control valve is
stuck. If not, check the
adjustment valve.

Adjustment valve

Close the gas inlet:

If the valve does not move:

(step motor)

Dismantle the step motor (screw not

Check the connections at both

sealed in). Trigger a demand and check

motor and control board (PCB).

that the valve opens during the ignition.

Change the motor. Replace the
control board (PCB).

Three way valve.

When heating is on:

If voltages are different:

Electrical supply to motor

230V ac between 1 and 2 of the motor.

Connections.

0

between 1 and 3.

About 25V ac to 35V ac between 2 and 3.

Control board (PCB).

9.6k

between 1 and 2.

When hot water is on:

Three way valve lead.

9.6k

between 1 and 3.

230V ac between 2 and 3 of the motor.

3 2 1

(1, 2 and 3 marked on

About 25V ac to 35V ac between 1 and 2.

the motor).

Thrust action of the motor.

Unfasten the clip (YES, no risk of water

If electrical supply is OK.

(remove gas control valve

leak), pull out the motor and leave it

but the spindle does not move

before testing)

plugged in.

Replace the motor, or replace

When hot water is on: the spindle should

the control board (PCB).

pull in. When heating is on : the spindle
should push out.

Domestic water flow

To test: Use a new detector and
connect it electrically in place of
the faulty one . Blow through to
simulate a demand for water.

COMPONENT TESTING DATA