20 replacement of parts – Glow-worm 30ci Plus User Manual

Page 45

Advertising
background image

45

4000123944-2

9646

Diagram 20.3

SENSING
TUBE

AIR PRESSURE
SWITCH

20.2 Fan, refer to Section 17.10

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

Remove the sealed chamber cover, refer to Section 17.5.

• Remove the fan, refer to Section 17.10.

20.3 Fan sensor, refer to diagram 17.8

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

• Lower the control panel, refer to Section 17.4.

• Remove the sealed chamber cover, refer to Section 17.5.

• Disconnect the electrical plug.

• Remove the 2 fan sensor retaining screws.

• Remove the fan sensor.

20.4 Air pressure switch

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

Remove the sealed chamber cover, refer to Section 17.5.

• Locate air pressure switch situated at the top right hand side,
see diagram 20.3.

• Remove air pressure switch tube from sensing probe on flue
hood.

Note: Do not fit tube until the air pressure switch is in position.

• Disconnect air pressure switch electrical connections.

• Unclip to remove air pressure switch.

20.5 Domestic water inlet filter

If the water flow rate through the appliance has reduced it may
be necessary to clean or replace the water inlet filter.

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

• Lower the control panel, refer to Section 17.4.

• Clean or replace the water inlet filter, refer to section 17.12.

20.6 Central Heating Filter

It may be necessary to clean or replace the central heating filter.

Before starting refer to the front of Section 20 Important
information.

• Clean or replace the central heating filter, refer to section
17.13
.

20.7 Cold water inlet restrictor

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

• Lower the control panel, refer to Section 17.4.

Drain down domestic hot water circuit of boiler only, refer to
relevant part of diagram 20.1
.

• Remove the retaining wire.

20 Replacement of Parts

ELECTRICAL
CONNECTORS

RETAINING
CLIPS

Diagram 20.4

COLD WATER INLET
RESTRICTOR

COLD WATER IN
ISOLATING VALVE

UNION NUTS

11929

11941

• Undo union nuts from boiler cold water in isolating valve.

• Clean and inspect restrictor, replace if necessary, see diagram
20.4.

20.8 Burner, refer to Section 17.9.

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

• Lower the control panel, refer to Section 17.4.

• Remove the sealed chamber cover, refer to Section 17.5.

• Remove the combustion chamber cover, refer to Section17.7.

• Remove the burner, refer to Section 17.9.

20.9 Burner injectors, refer to diagram 20.5.

Before starting refer to the front of Section 20 Important
information.

• Remove the front panel, refer to Section 17.3.

• Lower the control panel, refer to Section 17.4.

• Remove the sealed chamber cover, refer to Section 17.5.

• Remove the combustion chamber cover, refer to Section17.7.

• Remove burner from boiler, refer to Section 17.9.

• Remove and replace injectors as required.

Note: The injectors may be cleaned, remove injectors inspect
and clean. Do not use a wire or sharp instrument.

Note: Make sure that injector size, marked on each injector, is
the same as that given in ‘Section 1 Technical Data’ for the
type of gas being used.