Installation, 6 electrical connections – Glow-worm Clearly Heat Pumps - Standalone Module System User Manual

Page 17

Advertising
background image

0020096321_00 - 07/10 - Glow-worm

- 15 -

INSTALLATION

6 Electrical

connections

e

Incorrect installation can cause electric shock or
appliance damage. The electrical connection of
the appliance must be made only by a qualifi ed
engineer.

The appliance must be connected directly to an accessible,
fi xed, switched, electrical outlet.

The manufacturer declines any responsibility for damages to
persons or others caused by the incorrect installation of the
appliance earthing. This includes failure to comply with current
standards.

Electrical components have been tested to meet the equivalent
requirements of BSEN 7671 and the BEAB regulations.

Main board

20 mm max.

1

2

Key
1 Electrical

wires

2 Insulation

When you connect the electrical wires to a connector on the
electronic board:

• Maintain a maximum distance of 20 mm between the

connector and the outer insulation.

• If using single core wires are used ensure that they are

wrapped together in an insulating sheath.

6.1 Heat

pump

The cables connecting the isolator and the heat pump must be:
- suitable for a fi xed installation.
- weather resistant.
- equipped with wires adapted to appliance’s power rating.

• Connect the heat pump to an electrical panel via an

independent protection system (20A differential breaker with
at least 3 mm between each contact).

Additional protection may be required during installation to
ensure overvoltage category II.

6.1.1

Access to main board

B

A

2

1

Key
1 Handle
2 Box

• Remove the box (2) by pulling it toward you using the handle

(1).

6.2 Electrical

wiring

e

Insert the Ebus 24V cable and 230V power cable
in different casings.

B

A

5

4

3

2

1

6

Key
1

230 V supply connection terminal block

2

Ebus connection terminal

3

Clamp for Ebus cable

4

Clamp for 230 V power cable

5

Access hatch to electrical connections

6

Access hatch screw

• Remove the screw (6) from the access hatch (5).

• Open the access hatch (5).

Ebus Connection

• Connect a 2 x 0.75 mm ² cable to the heat pump’s BUS

terminal (2).

• Pass the cable through the cable clamp (3).

• Connect the Ebus cable to the Systempro control unit.

• Tighten the clamp.

230V Connection

• Connect a 3 x 2.5 mm ² cable to the heat pump’s power

terminal 230V (1).

• Pass the cable through the cable clamp (4).

• Connect the heat pump’s power cable to the installation’s

electrical panel: single-phase network 230V + neutral + earth.

• Close the access hatch with the screw (6).

• Tighten the clamp.