INSTALLATION

10.7.2

Domestic hot water

i

The lower the temperature of the hot water, the more
economical the heat pump.

This menu allows you to adjust the
maximum hot water temperature (value
adjustable between 35 °C and 65 °C -
factory setting: 65°C).

• Using the buttons

,

select Hot water on the screen.

• Press the button

to confi rm.

• Press the button

.

• Increase or decrease with the

buttons

to display the

desired value.

• Press the button

to confi rm.

• Press the button

.

10.7.3 Cooling

(*)

(*) Function not active for the UK

10.7.4 HP

Management

• Select

HP Management

on the

screen using the buttons

.

• Press the button

.

This menu is used to set the outside
temperature from which the heat pump
must turn off (value adjustable from
-10°C to 20°C, factory setting: 0°C).

• Press the button

.

• Increase or decrease with the

buttons

to display the

desired value.

• Press the button

.

This menu allows you to adjust the
installation’s maximum heating output
temperature (value adjustable between
30 ° C and 80 ° C - factory setting:
73°C).

• Press the button

.

• Press the button

.

• Increase or decrease with the

buttons

to display the

desired value.

• Press the button

to confi rm.

• Press the button

.

This menu allows you to select the
heating curve (value adjustable
between 0.2 and 4 - factory setting:
1.2), which allows you to obtain the
maximum heating demand for the usual
minimum outdoor temperature for the
region in which the sensor is installed.

• Using the buttons

,

select Heating curve adjustment on
the screen.

• Press the button

twice.

• Increase or decrease with the

buttons

to display the

desired value(s).

• Press the button

to confi rm.

b

Ensure that the heating curve setting is
compatible with the installation.

Heating curve

A

B

1

2

3

Key
1

Older properties with radiators

2

Standard/modern house with radiators

3

Highly insulated modern house with low temperature radiators
or underfl oor heating

A Heating

fl ow temperature (°C)

B External

temperature

• Press the button

twice.