INSTALLATION

6.4.4

Connection of the 2 port valve

1

3

L

N

230V~

1

3

L

N

REL1

1

3

L

N

REL2

1

3

L

N

REL3

1

2

L

N

REL4

1

2

L

N

REL5

1

2

L

N

IN1

When the 2 port valve is connected to REL3:

• Connect the neutral wire (blue) of the valve to the “N” of the

REL3 connector.

• Connect the live wire (brown) of the valve to the “L” of the

REL3 connector.

• Connect the earth wire (yellow/green) of the valve to the

earth of the REL3 connector.

• Electrically insulate the red and grey wires of the valve as

they are not used.

When the 2 port valve is connected to REL4 or 5:

• Connect the neutral wire (blue) of the valve to the “N” and

the live wire (brown) of the valve to the “L” of the REL4 or 5
connector.

• Connect the earth wire (yellow/green) of the valve to the

earth of the REL3 connector.

• Electrically insulate the red and grey wires of the valve as

they are not used.

Commissioning

• Open all the hydraulic circuits’ valves.

7

Filling the glycol circuit

b

Warning! Do not dispose of glycol into drains
and the environment.

b

We recommend that you use propylene glycol
enriched with corrosive inhibitors.

• Mix 1 part propylene glycol with 2 parts water. This

mixture ensures antifreeze protection down to an exterior
temperature of -15 °C.

• Use an antifreeze test kit to ensure accurate dosing.

Ø14

A

B

1

3

4

1

2

Key
1 Air

trap

2

Ø 14 mm fl at wrench (*)

3 Hose
4 Deposit

(*)

(*) Not

included

• Connect one end of the hose (3) to the trap (1).

• Insert the other end of the hose (3) into the container (4) in

order to recover any residual brine during the fi lling of the
circuit.

• Using

a

fl at wrench (2), open the trap (1) a ¼ turn.