Installation, 7 commissioning – Glow-worm Clearly Heat Pumps - Standalone System User Manual

Page 18

Advertising
background image

0020096321_01 - 02/11 - Glow-worm

- 16 -

6.5 Resetting

parameters

This feature allows you to reset the parameters of the control unit

(factory setting).

b

The resetting of factory settings is irreversible. Any

customised confi guration of the control unit will be lost.

1

Select Settings reset on

the screen.

2

Confi rm your choice.

7 Commissioning

i

Refer to the hydraulic module instructions for fi lling

the heating and glycol water circuits.

This menu allows you to carry out the necessary operations on

the appliances following installation.

1

Select Commissioning on

the screen.

7.1

Filling and venting the heating circuit

Filling the heating circuit allows the system to be pressurised.

Venting the heating circuit purges the air present in the heating

circuit.

Suitable external fi lling systems are shown diagrammatically, see

diagram below.

B

A

C

C

B

A

3

2

1

3

2

1

4

6

7

5

5

Key

1 Heating

fl ow isolating valve

2 Heating return isolating valve

3 Hydraulic

module

4 Temporary

fi lling loop (remove immediately after fi lling)

5 Drain

point

6 Back

fl ow prevention device

7 Tundish

A Heating return circuit

B Heating

fl ow circuit

C Domestic cold water supply in

INSTALLATION

EN