Maintenance, 11 trouble-shooting, 1 fault diagnosis – Glow-worm Clearly Heat Pumps - Standalone System User Manual

Page 22: 2 system fault codes

Advertising
background image

0020096321_01 - 02/11 - Glow-worm

- 20 -

MAINTENANCE

11 Trouble-shooting

11.1 Fault

diagnosis

The following checks should be performed before proceeding

onto specifi c diagnostics:

- Make sure that the electricity supply has not been interrupted

and that the appliance is connected correctly.

- Ensure that the isolating valves are open.

- Check that all external controls are connected correctly.

11.2 System fault codes

i

The faults described in this chapter should be carried

out by a qualifi ed engineer and if needed by the After

Sales Service.

Refer to the instructions for each element making up the

system for their fault codes.

Fault

codes Description

Cause

Solution

002

Failure in Ebus communication

between with the heat pump

The heat pump is not connected to the

control unit.

The heat pump is off .

Make sure the heat pump is connected to the control unit.

Ensure that there is no interruption to the electricity network

and that the heat pump is properly connected and turned on.

003

Failure in Ebus communication

between with the hydraulic module

The hydraulic module is not connected

to the control unit.

The hydraulic module is off .

Make sure that the hydraulic module is connected to the

control unit. Ensure that there is no interruption to the

electricity network and that the hydraulic module is properly

connected and turned on.

010

Heating circuit fl ow temperature sensor

failure (open circuit)

The sensor is defective or not

properly connected to the control unit

management or hydraulic module.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

011

Heating circuit fl ow temperature sensor

failure (short circuit)

The sensor is shorted.

012

Heating circuit fl ow temperature sensor

failure low temperature (open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

013

Heating circuit fl ow temperature sensor

failure low temperature (short circuit)

The sensor is shorted.

014

Domestic water tank temperature

sensor failure (open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

015

Domestic water tank temperature

sensor failure (short circuit)

The sensor is shorted.

021

Pressure too low <0.5 bar

There is a leak in the heating circuit.

The venting was not carried out

correctly.

Check that there are no leaks.

Drain the heating circuit. Remove air.

Fill the installation.

030

Failure in communication with the zone

1 wireless room thermostat.

The room thermostat is too far from the

control unit.

There is a problem with the batteries in

room thermostat.

Check the RF signal quality via the Climapro2 RF installer

menu.

Check the location of the thermostat.

Check that the thermostat’s batteries are installed in their

compartment.

Make sure the battery polarity is not reversed.

Make sure the batteries are not dead.

If so, replace them with new batteries

031

Failure in communication with the zone

2 wireless room thermostat.

032

Failure in communication with the zone

3 wireless room thermostat.

033

Failure in communication with the zone

4 wireless room thermostat.

034

Failure in communication with the zone

5 wireless room thermostat.

035

Failure in communication with the zone

6 wireless room thermostat.

036

Failure in communication with the

wireless outdoor sensor

The wireless outdoor sensor is too far

from the control unit.

Check the location of the outdoor sensor. Check that the

sensor’s power supply is correctly provided by a photovoltaic

cell.

MAINTENANCE

EN

Advertising