Installation, Multiple boiler chimney flue length, Flexicom 18sx flexicom 30sx – Glow-worm Flexicom sx User Manual

Page 13

Advertising
background image

0020107231_04 - 12/14 - Glow-worm

INSTALLATION

- 13 -

4.2.4

Multiple boiler chimney flue

Ø 60/100 mm (C43 type installation)

The flue connecting from the appliance to

the flue system must be supplied from the

manufacturer of the boiler.

C43 flue systems must not be a 'pressurised

system' but act under natural draught

principles

C43 type flue systems must have their

own condensate drain fitted and not allow

condensate to mix into other appliances

Multiple Boiler Chimney Flue Length

The flue length must be calculated and installed according to

the relevant standards EN 13384-1 and 2 (C43 flue systems

only) with reference to the table below and the manufacturers

instructions supplied.

The appliance maximum flue length must be included when

calculating the overall design of the flue system.
NOTE: The horizontal flue terminal must be removed.

L

B

A

1

2

3

4

5

Key

1 Pressure balancing system

2 Air-inlet pipe

3 Collector pipe

4 Boiler

5 Inspection hatch

A Final storey

B Ground floor

Type

Max length (L)

Ø 60/100

8 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.

Flexicom

18sx

Flexicom

30sx

Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)

4.26

4.26

At Max Thermal
Load (80C°/60°C)

8.24

13.95

Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)

33.2

33.2

At Max Thermal
Load (80C°/60°C)

63.0

87.4

Advertising