Maintenance, 7 condensate trap, 8 casing panel seal check – Glow-worm Flexicom sx User Manual
Page 32

0020107231_04 - 12/14 - Glow-worm
MAINTENANCE
- 32 -
Diagram 12.11
12815
13006
Diagram 12.12
14737
SECURING
SCREW
SERVICE
FILL LEVEL
CONDENSATE
TRAP
Diagram 12.10
13007
12.7 Condensate Trap
NOTE: If the functional checks did not indicate poor
combustion then it is not necessary to service this
component.
The condensate trap does not normally need removing during
servicing unless the service fill level is at full, see diagram
12.12.
To flush the condense drain carefully pour water into the heat
exchanger and check that water flows freely to drain.
12.8 Casing panel seal check
NOTE: If the functional checks did not indicate poor
combustion then it is not necessary to service this
component.
Check the condition of the seal and replace if worn or damaged.
To replace remove the old seal and thoroughly clean the casing
surfaces. Fit the new seals, these are supplied to the correct
lengths and are in four pieces, for use on the sides, top and
bottom.