Installation, 7 vented dhw system, 8 unvented dhw system – Glow-worm Flexicom sx User Manual

Page 16: 10 safety valve, 11 expansion vessel

Advertising
background image

0020107231_04 - 12/14 - Glow-worm

INSTALLATION

- 16 -

15723

Diagram 5.3

Water System - Domestic Hot Water

5.6 Domestic Water Cylinder

SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE

AND SHOULD NOT BE USED.

The domestic hot water cylinder must be of the double feed

indirect coil type. It must be suitable for working at a gauge

pressure of 0.35bar above the safety valve setting.

5.7 Vented DHW System

General - All domestic hot water circuits, connections, fittings

must be in accordance with the relevant standards and water

supply regulations.

For GB: Guidance G17 to G24 and recommendation R17 to

R24 of the Water Regulations Guide

(for Scotland, the Water

Byelaws 2000, Scotland)

.

For IE: The current edition of I.S.813 “Domestic Gas

Installations”.

5.8 Unvented DHW System

General - All domestic hot water circuits, connections, fittings

must be in accordance with the relevant standards and water

supply regulations.

For GB: Guidance G17 to G24 and recommendation R17 to

R24 of the Water Regulations Guide.

For IE: The current edition of I.S.813 “Domestic Gas

Installations”.

Where a storage system will not have a vent to atmosphere

the installation must comply with the building regulations and

the Water Supply (water fittings) Regulations 1999 and water

byelaws 2000, Scotland

, see also the current issue of BS5546

and BS6700.

If fitting to an existing system the local authority should be

informed.

Water System - Sealed Central Heating

System

5.9 Sealed Water Systems

The installation must comply with the appropriate requirements

of the current issue of BS4814, BS5449, BS6759, BS6798 and

BS7074 Part 1 and 2.

See diagram 5.4 for a suggested layout.

5.10 Safety Valve

The safety valve is an integral part of the boiler and it cannot

be adjusted.

The pipe from the safety discharge valve must

not discharge above an entrance, window or any type of public

access area.

5.11 Expansion Vessel

The boiler has an integral expansion vessel with a capacity of 8

litres (1.76 gallons), with a charge pressure of 0.5bar.

NOTE: The expansion vessel volume depends on the total

water system volume and the initial system design pressure.

In GB, Guidance on vessel sizing is also given in the current

issue of BS5449 and BS7074 Part 1.

In IE, current edition of I.S.813 “Domestic Gas Installations”