Installation, 2 clearances, 3 timber frame buildings – Glow-worm Flexicom sx User Manual

Page 9: 4 combustible material, 5 room ventilation, 6 cupboard or compartment ventilation, 7 airing cupboard installation, 8 roof restricting installation

Advertising
background image

0020107231_04 - 12/14 - Glow-worm

INSTALLATION

- 9 -

3 Boiler location, Clearances and

Ventilation

3.1 Location

This boiler is not suitable for outdoor installation.

This boiler may be installed in any room, although particular

attention is drawn to the installation of a boiler in a room

containing a bath or shower where reference must be made to

the relevant requirements.

This boiler is suitable for installation in bathroom zones 2 and 3.

In GB this is the current I.E.E. WIRING REGULATIONS and

BUILDING REGULATIONS.

In IE reference should be made to the current edition of I.S.813
“Domestic Gas Installations” and the current ETCI rules.

3.2 Clearances

The boiler should be positioned so that at least the minimum

operational and servicing clearances are provided, see diagram

3.1.

Additional clearances may be beneficial around the boiler for

installation and servicing.

For flue installations where external access is not practicable,

consideration should be given for the space required to insert

the flue internally, which may necessitate clearance larger than

those specified in diagram 3.1.

3.3 Timber Frame Buildings

If the boiler is to be installed in a timber frame building it should

be fitted in accordance with the Institute of Gas Engineers

document IGE/UP/7/1998. If in doubt seek advice from local

gas undertaking or Glow-worm.

3.4 Combustible Material

The boiler and flue are suitable for installation onto and through

combustible materials provided that:-

1) Minimum 5mm clearance is maintained around the

circumference of the flue (air intake).

2) The combustible surface and fixings are suitable for

supporting the load.

3) The minimum clearances from the boiler case are

maintained.

3.5 Room Ventilation

The boiler is room sealed so a permanent air vent is not

required.

3.6 Cupboard or Compartment Ventilation

Due to the high efficiency and low casing temperature of this

boiler, cupboard or compartment ventilation is not necessary.

• Existing ventilation should be investigated for its purpose

before removing.

Diagram 3.1

13127

3.7 Airing Cupboard Installation

If the boiler is to be installed in an airing cupboard it is not

required to separate the boiler with a non-combustible partition.

However, installation and servicing clearances must be

maintained, and the boiler kept clear of any clothing. Details of

essential features of cupboard/compartment design including

airing cupboard installations are given in BS 6891. In IE the

current edition of IS 813.

3.8 Roof Restricting Installation

It is not necessary to ensure sufficient clearance between

the boiler and combustible materials or components. This is

because the temperature of the boiler will always be less than

85

o

C due to its nominal heat output.

Advertising