Chapter 4 Parameters|

4-52

Revision July 2008, EG03, SW V1.06

Group 6: Protection Function Parameters

06 - 00

Over-voltage Stall Prevention

Factory Setting: 780.0

Settings

660.0V~820.0VDC
00: Disabled

This parameter selects the voltage level for the Over-Voltage Stall Prevention function.

During decelerations, the DC bus voltage may exceed its maximum allowable value due to

motor regeneration. When this function is enabled, the AC drive will stop decelerating and

maintain a constant output frequency. The AC drive will only resume deceleration when the

voltage drops below the preset value.

With moderate inertial loads, the over-voltage stall prevention will not occur and the

deceleration time should be equal to Pr.1-10. With high inertial loads, the AC drive will

automatically extend the deceleration time due to the step function shown below. If the

deceleration time is critical for the application, then dynamic braking resistors should be used.

Output frequency

Deceleration characteristic
when Over-voltage stall
prevention enabled

Frequency held

Deceleration Time

Time

06 - 01

Over-current Stall Prevention during Acceleration

Unit: 1

Settings

20~250%

Factory Setting: 150%

This parameter selects the percentage of allowable over-current during acceleration before the

stall prevention is enabled.

During acceleration, the AC drive output current may increase abruptly and exceed the value

specified by Pr.06-01 due to rapid acceleration or excessive load on the motor. When this

function is enabled, the AC drive will stop accelerating and maintain a constant output

frequency. The AC drive will only resume acceleration when the current drops below the value

set in Pr.06-01 (please see the graph below).