Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-65

Master frequency command

Output frequency

Output voltage

output current

Synchronization attained

Time

08-07

Output voltage

Output frequency

Actual V/f output

V/f curve setting

08 - 08

BB Speed Search Method

Factory Setting: 00

Settings

00: Trace from top downward
01: Trace from bottom upward

This parameter determines BB speed search method when multi-function input terminal 04-00

to 04-03 is set to BB External interrupt (11 or 12) and activates.

BB speed search method is the same with restart speed search after momentary loss power.

08 - 09

Auto Restart Times After Fault

Settings

00 ~10

Factory Setting: 00

This parameter determines the times of auto restart after fault.

When AC drive occurs fault (OV, OC or OCC) and fault disappeared automatically, this

parameter allows AC drive reset and runs with the parameter that is set before fault occurred.

If fault occurred times exceed 08-09 setting, AC drive will reject to restart and need to reset by

users to keep on running.