Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-81

3.5 Address list:

The contents of available addresses are shown as below:

Content Address

Function

AC drive

Parameters

GGnnH

GG means parameter group, nn means parameter number,
for example, the address of Pr 04-01 is 0401H. Refer to
chapter 5 for the function of each parameter. When reading
parameter by command code 03H, only one parameter can
be read for one time.

Bit 0-1

00B: Disabled
01B: Stop
10B: Run
11B: Jog + Run

Bit 2-3

Reserved

Bit 4-5

00B: Disabled
01B: FWD command
10B: REV command
11B: Direction change command

Bit 6-7

00B: 1st step acce/decel speed
01B: 2nd step acce/decel speed
10B: 3rd step acce/decel speed
11B: 4th step acce/decel speed

Bit 8-11

0000B: Master speed
0001B: 1st step speed
0010B: 2nd step speed
0011B: 3rd step speed
0100B: 4th step speed
0101B: 5th step speed
0110B: 6th step speed
0111B: 7th step speed
1000B: 8th step speed
1001B: 9th step speed
1010B: 10th step speed
1011B: 11th step speed
1100B: 12th step speed
1101B: 13th step speed
1110B: 14th step speed
1111B: 15th step speed

Bit 12

Select Bit6~11 function

2000H

Bit 13-15

Reserved

2001H

Freq. command

Bit 0

1: EF (external fault) on

Bit 1

1: Reset

Command

Write only

2002H

Bit 2

0: BB OFF
1: BB ON