Chapter 4 Parameters|
Revision July 2008, EG03, SW V1.06
4-55
When Pr.6-06 is set for 1 or 2 and the output current exceeds Pr.7-02 for the time set in Pr.6-
07, the drive will fault with an OL1.
The common electronic thermal reaction time (150% output current for 1 minute) is shown in
the chart below. The actual reaction time will vary depending on output current.
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
Load
factor
(%)
Operation
Time(min)
0
20 40 60 80 100 120 140 160 180 200
06 - 08
Low Current Detection Level
Unit: 1
Settings
00~100% (00 disabled)
Factory Setting: 00
06 - 09
Low Current Detection Time
Unit: 0.1
Settings
0.1~ 3600.0 Sec
Factory Setting: 10.0
06 - 10
Low Current Detection Treatment
Factory Setting: 01
Settings
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
These parameters set the low current detection mode, time, and operation.
06 - 11
Present Fault Record
06 - 12
2nd Most Recent Fault Record
06 - 13
3rd Most Recent Fault Record
06 - 14
4th Recent Fault Record
Factory Setting: 00