Chapter 4 Parameters|

4-88

Revision July 2008, EG03, SW V1.06

10 - 07

Primary Low Pass Filter Time

Unit: 0.1

Settings

0.0~2.5 Sec

Factory Setting: 0.0

This parameter determines primary Low Pass filter time.

Output frequency of PID controller will filter by primary low pass function. This function could

decrease change of output frequency. A long primary low pass time means filter degree is high

and vice versa.

Unsuitable primary low pass filter time setting may cause system oscillation.

10 - 08

PID Feedback Signal Range

Unit: 0.01

Settings

0.01~160.00Hz

Factory Setting: 600.00

This parameter setting could allow the maximum of PID deviation.

If PID function is normally, it should control the detective value to target value accurately in the

certain time. If AC drive can’t control deviation in the 10-08 setting range during 10-07 setting

time, it means PID feedback control is abnormal. The treatment is set as 10-10.

10 - 09

PID Feedback Signal Fault Treatment Time

Unit: 0.1

Settings

0.0~3600.0 Sec

Factory Setting: 0.0

This parameter is to set the detection time of abnormal PID derivative. If PID deviation

detection time is set to 0.0, the function is disabled.

10 - 10

PID Feedback Signal Fault Treatment

Factory Setting: 01

Settings

00: Warn and RAMP stop
01: Warn and COAST stop
02: Warn and keep operating

This parameter is to set treatment of the abnormal PID deviation.

10 - 11

V/F Curve Selection

Factory Setting: 00

Settings

00: Determined by group 1
01: 1.5 power curve
02: 1.7 power curve
03: 2 power curve
04: 3 power curve