Delta Electronics AC Motor Drive VFD-G User Manual

Page 104

Advertising
background image

Chapter 4 Parameters|

Revision July 2008, EG03, SW V1.06

4-53

When the over-current stall prevention is activated, the acceleration time of the AC drive will

be longer than the time set in Pr. 01-09.

Over-current Stall
Prevention during
acceleration

06-01

Current

Output
frequency

Over-current stall
prevention during
acceleration,
frequency held

Time

Over-current Stall Prevention during Acceleration

06 - 02

Over-current Stall Prevention during operation

Unit: 1

Settings

20~250%

Factory Setting: 150%

This parameter selects the percentage of allowable over-current during operation before the

stall prevention function is enabled.

If the output current exceeds the value specified in Pr.06-02 when the drive is operating at

steady state speed, the drive will decrease its output frequency to prevent the drive from

faulting with an OC. Once the current falls below the value specified in Pr.06-02, the drive will

then accelerate to catch up with the command frequency.

Over-current Stall
Prevention during
operation 06-02

Current

Output
frequency

Over-current Stall
Prevention during
operation, output
frequency decrease

Time

Over-current Stall Prevention during Operation