FORM NO. L-21204-C-0908

8

FIGURE 5

Alarm Output Connections

Alarm Out

RSTC

RSTC

To PL C Input

VD C Common

VD C*

(See Specifications for
maximum voltage.)

R

(See Note.)

User Supplied

User Supplied

NOTE: The minimum value of resistor (R) is 7 x VDC.

VD C Common

VDC*

(See Specifications for
maximum voltage.)

(See Note.)

User Supplied

User Supplied

R

External Indicator

VD C Common

VDC *

(See Specifications for
maximum voltage.)

(See Notes.)

User Supplied

User Supplied

External

Coil

1N4002

Alarm Output Tied to External Indicator

Alarm Output Tied to PLC Input.

Alarm Output Tied to External Inductive Coil

Alarm

Common

Alarm Out

Alarm

Common

RSTC

Alarm Out

Alarm

Common

NOTE: The minimum value of Resistor (R) is equal to VDC divided by the maximum
current limit of the Indicator. Maximum current limit of the indicator must be less
than the current limit of the alarm output (See Specifications for maximum current).

NOTE: Be sure the current requirement of the External Coil does not exceed the
capability of the alarm output (See Specifications for maximum current.

Any inductive load such as relay coil must have a 1N4002, or equivalent, diode
across it as shown.

* To isolate the Alarm Output signals use power

supply that is separate from the RSTC power supply.