Note: The Universal Safety Controller HUB should

be examined on a daily basis for correct operation.

Malfunctioning units should be removed from further

operation.

Installation Procedure

1. Determine the mounting location for the

Universal Safety Controller HUB (HUB). It

should located in a protective panel as far away

from electrical noise as possible.

2. Provide a 24vdc power supply with enough

capability to power the HUB and any 24v

devices you attached to it.

3. Determine the devices that will be wired to the

HUB and wire them up to the HUB in the same

order as the Model# states. (See page 6 and

example wiring pages for additional information.)

OK

Total Devices 08

Indicates Channel C

output Status

Indicates Mute-Out or

Bypass modes

Indicates Channel D

output Status

US

B p

ort f

or

pro

gra

mm

ing

Ex

pa

ns

ion

Po

rt

St

at

us

O

ut

pu

ts

Ch

an

ne

l D

ou

t

Po

we

r I

np

ut

Ea

rth

G

ro

un

d

3

C

ha

nn

el

C

Sa

fe

ty

O

ut

pu

ts

Po

we

rI

N

pa

ss

-th

ro

ug

h

Optional RJ-45 Jack

Device connection

Au

x

C

ha

nn

el

C

ou

t

FN1 & FN2 Function

buttons

Operation

1. Upon power up, the Software Rev# will come up

for a short time.

2. The 2 computers (Master & Slave) communicate

with each other to check for faults.

3. If no Faults are detected, the Universal Safety

Controller HUB will operate as normal.

How to use the Diagnostics Display

Operational Status: Shows current status of all devices,

showing the first device found that is opposite its NORMAL

status.

(Press FN1 one time)

Terminal Status: Shows status of each Terminal on both the

A and B side of the Safety Hub. 0=open, 1=closed. You can-

not see the Terminal status of 3 or 4 wire devices since they

are pulsed (Press FN2 to scroll through all Terminals)

(Press FN1 one time)

Device Status: Shows status of each Device as determined

by the Master and Slave computers. A=Slave & B=Master.

1=active (Press FN2 to scroll through all Devices)

(Press FN1 one time)

A/D Status: Analog inputs status for Mat devices only (Press

FN2 to scroll though all channels of A/D)

(Press FN1 one time to return to Operational Status if no TIM-

ERS are active)

Device Timer Value: Shows current Timer setting if 1/10th

of seconds. (Press FN2 to scroll through all timer available)

(PROGRAM MODE: Press FN1 & FN2 together, now FN1 =

+, FN2 = -, when finished Press FN1 & FN2 together again)

(Press FN1 one time to return to Operational Status)