Outputs (channels c,d,e) device list – Pinnacle Systems Universal Safety Controller HUB User Manual

Page 8

Advertising
background image

Page 3 of 18

OUTPUTS (Channels C,D,E) Device List

0)

No Output Device Selected

1‐8) 

Channel E1‐8

Solid State opto Relays (8)

Provides 8 +24vdc outputs (NOT 
monitored).   1/2A@24vdc resistive load 
(optional 1A@24vdc). (E1 is always used 
as a status indicator for Channel D1‐2 [E1 
active when D1/D2 active])

16)          

Channel C

Mechanical Safety relays

For any Device to control C output. C1, 
C2, C3 are mechanically linked.

32)

Channel D

Solid‐State Safety relays

For any Device to control D output. D1, 
D2 require EDM option if linked to 
external mechanical relays.

64)

Channel C4‐6

on 2

nd

 Safety Hub

Channel C Safety Outputs found on 2

nd 

Safety Hub         

128)

Channel D3‐4

on 2

nd

 Safety Hub 

Channel D Solid‐State Safety outputs 
found on 2

nd

 Safety Hub

240)

Channel C

Timer ON

Timer function used to hold Output C ON

241)

Channel C

Timer OFF

Timer function used to hold Output C OFF

242)

Channel D

Timer ON

Timer function used to hold Output D ON

243)

Channel D

Timer OFF

Timer function used to hold Output D OFF

251)

Channel C/D

For Run Devices to Latch output C ON, D 
OFF

252)

Channel C/D

For RUN or Limit Switch devices Latch 
output D ON, and C OFF.

253)

Channel C/D

For RUN or Limit Switch devices to shut 
down both C and D outputs.

254)

Channel C/D

For ESTOP Devices to Control both C & D 
outputs

255) 

Faults all Outputs (shuts down) when this 
Device OPENS.