Remote output on/off control – AMETEK ASD Series User Manual
Page 53
Advertising

Sorensen ASD Series
Operation
M551177-01 Rev A
3-15
+
-
1
2
3
LOAD
SUPPLY
OUTPUT
TERMINALS
Pin 1: Sense(+)
Pin 3: Sense(-)
Figure 3-17. Remote Sensing Operation at the Load
3.8
REMOTE OUTPUT ON/OFF CONTROL
Remote output on/off control may be accomplished by contact closure or
by an isolated external DC voltage source.
3.8.1 REMOTE OUTPUT ON/OFF BY CONTACT CLOSURE
Output is on when contacts are closed. Connection requirements are as
follows:
Terminals 14 and 17 on unit with digital option board (Figure 3-18)
Terminals 5 and 6 on unit with SG compatible option board (Figure 3-19)
Terminal 2 and 3 on unit with EtherCAT option board (Figure 3-20)
1
13
25
14
17
ON/OFF
Figure 3-18. Remote Output ON/OFF Control by Contact Closure (Digital Option Board)