Section 2 • register table, General, Conventions – Basler Electric BE1-700 Modbus Protocol User Manual
Page 29: Register table - ordered by register number, Section 2, Register table -1

9376700991 Rev D
BE1-700 Modbus™ Protocol
2-1
SECTION 2 • REGISTER TABLE
Mapping BE1-700 Parameters into Modicon Holding Register Address
Space
General
Parameters are mapped into the holding register address space (40001 - 49999) in blocks according to
access type.
Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers are
legal but no action will be taken (the write is ignored).
Conventions
The Data Format column uses the following abbreviations:
ASC(x)
- ASCII string, where x = the maximum defined string length
BM(x)
- Bit-map, where x = the number of related bits
FP
- Floating point
INT
- Integer (16-bit integer)
LI
- Long Integer (32-bit integer)
SI
- Short Integer (8-bit integer)
The
Notes column uses the following abbreviations:
GRP
Group Template Member
FLT
Fault Template Member
RPT
Report Template Member
NS
Not Supported
TS
Time Stamp format: MSEC of the day (0 to 86,400,000 ms) and DAYs since 01/01/1984.
PS
Effective only when the Password Security parameter is enabled. See REGISTER
DETAILS for Password Security holding register 40989.
PW
Effective for any communication port active with ASCII protocol and for the Modbus™ port
(COM 2) when Password Security is enabled.
Register Table - Ordered By Register Number