Basler Electric BE1-700 Modbus Protocol User Manual
Page 68

3-20
BE1-700 Modbus™ Protocol
9376700991 Rev D
47367
System Status (Logic Var 0 to 15)
BM(16)
Read only:
Bit 15 - 50TQ picked-up
Bit 14 - 150T neutral picked-up
Bit 13 - 50T neutral picked-up
Bit 12 - 150T phase picked-up
Bit 11 - 50T phase picked-up
Bit 10 - 51Q tripped
Bit 9 - 151 neutral tripped
Bit 8 - 51 neutral tripped
Bit 7 - Spare
Bit 6 - 51 phase tripped
Bit 5 - 150TQ tripped
Bit 4 - 50TQ tripped
Bit 3 - 150T neutral tripped
Bit 2 - 50T neutral tripped
Bit 1 - 150T phase tripped
Bit 0 - 50T phase tripped
47368
System Status (Logic Var 16 to 31)
BM(16)
Read only:
Bit 15 - Logic always FALSE
Bit 14 - Spare
Bit 13 - 79SCB
Bit 12 - 79RST
Bit 11 - 79LO
Bit 10 - 79RNG
Bit 9 - 79C
Bit 8 – 79P
Bit 7 - 143
Bit 6 - 43
Bit 5 - 51Q picked-up
Bit 4 - 151N picked-up
Bit 3 - 51N picked-up
Bit 2 - Spare
Bit 1 - 51 phase picked-up
Bit 0 - 150TQ picked-up
47369
System Status (Logic Var 32 to 47)
BM(16)
Read only:
Bit 15 - Virtual Output 15 status
Bit 14 - Virtual Output 14 status
Bit 13 - Virtual Output 13 status
Bit 12 - Virtual Output 12 status
Bit 11 - Virtual Output 11 status
Bit 10 - Virtual Output 10 status
Bit 9 - Virtual Output 9 status
Bit 8 - Virtual Output 8 status
Bit 7 - Virtual Output 7 status
Bit 6 - Virtual Output 6 status
Bit 5 - Virtual Output 5 status
Bit 4 - Virtual Output 4 status
Bit 3 - Virtual Output 3 status
Bit 2 - Virtual Output 2 status
Bit 1 - Virtual Output 1 status
Bit 0 - Virtual Output A status