BE1-700 Modbus™ Protocol
4-3
ASCII Command
Modbus™ Registers
S#-792=<second auto reclose delay>
40408-40409
S#-793=<third auto reclose delay>
40410-40411
S#-794=<fourth auto reclose delay>
40412-40413
S#-79R=<reset time delay>
40414-40415
S#-79F=<reclose fail time delay>
40416-40417
S#-79M=<max reclose time>
40418-40419
S#-79P=<pilot time delay>
40420-40421
S#-79SCB=<sequence control>
40422
S#-81=<pickup>,<time delay>,<mode>
40460-40461, 40462-40463, 40464
S#-181=<pickup>,<time delay>,<mode>
40465-40466, 40467-40468, 40469
S#-281=<pickup>,<time delay>,<mode>
40470-40471, 40472-40473, 40474
S#-381=<pickup>,<time delay>,<mode>
40475-40476, 40477-40478, 40479
S#-481=<pickup>,<time delay>,<mode>
40480-40481, 40482-40483, 40484
S#-581=<pickup>,<time delay>,<mode>
40485-40486, 40487-40488, 40489
S#-81INH=<Va>,<VQ>,<overfreq>,<underfreq>
40490-40491, 40492-40493, 40494-40495,
40496-40497
S#-62=<time delay 1>,<time delay2>
40359-40360, 40361-40362
S#-162=<time delay 1>,<time delay2>
40363-40364, 40365-40366
S#-24=<pickup>, <time delay>, <reset delay>
40516-40517, 40518-40519, 40520-40521
S#-25=<delta volts>, <phase angle>,
<frequency>, <mode>
40522-40523, 40524-40525, 40526-40527, 40528
S#-25VM=<live volts>, <dead volts>, <time
delay>, <mode1>
40529-40530, 40531-40532, 40533-40534,
40535-40536
SA-BKR1=<mode>,<alarm limit>
41096, 41097-41098
SA-BKR2=<mode>,<alarm limit>
41099, 41100-41101
SA-BKR3=<mode>,<alarm limit>
41102, 41103-41104
SA-DIP=<alarm level>
41259-41260
SA-DIN=<alarm level>
41261-41262
SA-DIQ=<alarm level>
41263-41264
SA-LGC=<alarm number>
41269-41270
SA-MAJ=<alarm number>
41265-41266
SA-MIN=<alarm number>
41267-41268
SA-RESET=<reset Alarm Logic>
41419-41424, 41427-41432
SA-24 = <Volts / Hertz alarm level>
41247
SB-DUTY=<exponent>,<dmax.>,<blk bkr logic>
41092-41093, 41094-41095, 41110-41115,
41118-41123
SB-LOGIC=<breaker close logic equation>
41126-41131, 41134-41139
SG-BL=<LCD timer>
41218
SG-CLK=<date format>,<time format>
<dst enable>
41272, 41273, 41274
SG-COM0=<baud rate>,<flow control>,<page
length>,<ack>
40962, 40964, 40965, 40966
SG-COM1=<baud rate>,<relay address>,<flow
control>,<page length>,<ack>
40971, 40972,40973, 40974, 40975
SG-COM2=<baud rate>,<relay address>,,,,,
<parity>,<remote delay>,<stop bits>
40980, 40981, 40986, 40987, 40988
SG-CTP=<ratio>
41021
SG-CTG=<ratio>
41022
SG-VTP=<VT ratio>,<connection>,<27/59
mode>,<51/27R mode>
41033-41034, 41035-41036, 41037-41038,
41039-41040
SG-VTX=<aux VT ratio>,<connection>
41041-41042, 41043-41044
SG-NOM=<nom volts>,<nom amps>
40602-40603, 40604-40605
SG-DIP=<alarm interval>,<calculation method>
41275
SG-DIN=<alarm interval>,<calculation method>
41276
SG-DIQ=<alarm interval>,<calculation method>
41277
SG-FREQ=<frequency>
41018
SG-HOLD=<output hold enable>
41284