System data setting parameters, System data setting parameters -14 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 62

3-14
BE1-700 Modbus™ Protocol
9376700991 Rev D
2 - 1200 Baud (Do not select for Port 2 Modbus communications)
3 - 2400 Baud
4 - 4800 Baud
5 - 9600 Baud
6 - 19K Baud
40981
Serial Port 2 Relay Address
INT
Read and Write: 0 to 65,534
40964
Serial Port 0 Software Flow Control
SI
Read: 0 if XON / XOFF Control is disabled, 1 if XON / XOFF Control is enabled
Write: 0 to disable XON / XOFF Control, 1 to 255 to enable XON / XOFF Control
40965
Serial Port 0 Page Length
SI
Read and Write: 0 for disabled, 1 to 40 for number of lines / page
40966
Serial Port 0 Acknowledgement Format
SI
Read: 0 if No acknowledge, 1 if Acknowledge enabled
Write: 0 for No acknowledge, 1 to 255 to enable acknowledge
40986
Serial Port 2 Modbus Parity
SI
Read and Write: 0 for No parity, 1 for Even parity, 2 for Odd parity
40987
Serial Port 2 Modbus Remote Delay
SI
Read and Write: 1 to 20: 10 to 200 milliseconds
40988
Serial Port 2 Modbus Stop Bits
SI
Read and Write: 1 for One stop bit, 2 for Two stop bits
40989
Password Security
SI
Read and Write: Default value is disabled, 1 to enable Password Security.
When Password Security is enabled, relay parameters can be changed via Modbus only
if access is obtained via the Access Password and Access Request holding registers and
released via the Exit register with value 89 (ASCII character 'Y').
0 to disable Password Security.
When Password Security is disabled, no access is required (Access Password, Access
Request, and Exit holding registers have no effect) and no password protection is used.
Global Parameters, holding registers 40080 - 40099 (ASCII command GS-PW) have no
effect on the Modbus serial port, COM2.
System Data Setting Parameters
41018
System Frequency
SI
Read and Write: 50 for 50 hertz, 60 for 60 hertz
41019-20
Phase Rotation
ASC(3)
Read and Write: ABC for ABC rotation, ACB for ACB rotation
41021
Phase CT Ratio
INT
41022
Ground CT Ratio
INT
Read and Write: 1 to 50,000
41033-34
Phase VT Ratio
FP
41041-42
Auxiliary VT Ratio
FP
Read and Write: 1.00 to 10000
41035-36
27/59 Voltage Sensing Mode
ASC(3)
41037-38
51/27R Voltage Sensing Mode
ASC(3)
Read and Write: PP for Line, PN for Phase