Basler Electric BE1-700 Modbus Protocol User Manual
Page 52

3-4
BE1-700 Modbus™ Protocol
9376700991 Rev D
Bit 9 - Virtual Output 9 status
Bit 8 - Virtual Output 8 status
Bit 7 - Virtual Output 7 status
Bit 6 - Virtual Output 6 status
Bit 5 - Virtual Output 5 status
Bit 4 - Virtual Output 4 status
Bit 3 - Virtual Output 3 status
Bit 2 - Virtual Output 2 status
Bit 1 - Virtual Output 1 status
Bit 0 - Virtual Output A status
Mask and Term - Fourth Register (Logic Var 48 to 63)
BM(16)
Bit 15 - Target Reset key
Bit 14 - Output circuit monitor
Bit 13 - Alarm minor
Bit 12 - Alarm major
Bit 11 - Alarm logic
Bit 10 - 101 SC
Bit 9 - 101C
Bit 8 - 101T
Bit 7 - 27 neutral picked-up
Bit 6 - 27 neutral tripped
Bit 5 - 162
Bit 4 - 62
Bit 3 - Input 4 status
Bit 2 - Input 3 status
Bit 1 - Input 2 status
Bit 0 - Input 1 status
Mask and Term - Fifth Register (Logic Var 64 to 79)
BM(16)
Bit 15 – 59 phase tripped
Bit 14 - BF tripped
Bit 13 – BF picked-up
Bit 12 - 24 volts per hertz picked-up
Bit 11 – 24 volts per hertz tripped
Bit 10 - 47 picked-up
Bit 9 - 47 tripped
Bit 8 - 127 phase picked up
Bit 7 - 27 phase picked up
Bit 6 - 127 phase tripped
Bit 5 - 27 phase tripped
Bit 4 - 159 phase picked-up
Bit 3 - 59 phase picked-up
Bit 2 - Settings Group 1
Bit 1 - Settings Group 0
Bit 0 - Alarm Reset key
Mask and Term - Sixth Register (Logic Var 80 to 95)
BM(16)
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - 25 tripped
Bit 12 - 25 voltage monitor 1 pickup
Bit 11 - 60FL
Bit 10 - 581 tripped
Bit 9 - 481 tripped
Bit 8 - 381 tripped
Bit 7 - 281 tripped
Bit 2 - 181 tripped
Bit 1 - 81 tripped
Bit 0 - 159X picked-up
Bit 0 - 59X picked-up