Basler Electric BE1-700 Modbus Protocol User Manual
Page 50

3-2
BE1-700 Modbus™ Protocol
9376700991 Rev D
41809
Programmable 62 Timer Logic Mode
INT
41842
Programmable 162 Timer Logic Mode
INT
Read and Write:
0 for disabled
1 for Pickup / Dropout
2 for One-Shot Non-Retriggerable
3 for One-Shot Retriggerable
4 for Oscillator
5 for Integrating
6 for Edge Triggered Latch
41875
Programmable 27P Logic Mode
INT
41909
Programmable 127P Logic Mode
INT
41943
Programmable 59P Logic Mode
INT
41977
Programmable 159P Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled - Undervoltage or overvoltage on one or more phases causes pickup
2 for enabled - Undervoltage or overvoltage on two or more phases causes pickup
3 for enabled - Undervoltage or overvoltage on all three phases causes pickup
41892
Programmable 27X Logic Mode
INT
41960
Programmable 59X Logic Mode
INT
41994
Programmable 159X Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled - Fundamental Vx input
2 for enabled - 3Vo phase input
3 for enabled - 3
rd
harmonic, Vx input
43236
Programmable 81 Logic Mode
INT
43253
Programmable 181 Logic Mode
INT
43270
Programmable 281 Logic Mode
INT
43287
Programmable 381 Logic Mode
INT
43304
Programmable 481 Logic Mode
INT
43321
Programmable 581 Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
43338
Programmable 47 Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
43355
Programmable 24 Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
43372
Programmable 25 Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
42062
Programmable Settings Group Logic Mode
INT
Read and Write:
0 for all setting groups disabled except Group 0
1 for selecting setting group via pulsed input logic
2 for selecting setting group via sustained input logic