Logic mask and terms, Logic mask and terms -3 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 51

9376700991 Rev D
BE1-700 Modbus™ Protocol
3-3
42111
Programmable 43 Virtual Switch Logic Mode
INT
42112
Programmable 143 Virtual Switch Logic Mode
INT
Read and Write:
0 for disabled
1 for on / off / pulse (all)
2 for on / off
3 for pulse
42115
Programmable 101 Virtual Breaker Control Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
Logic Mask and Terms
Each set bit in the "mask" parameter indicates a significant variable in the equation. A corresponding bit in
the "term" parameter indicates that the variable must be TRUE / 1 if set or FALSE / 0 if not set.
Mask and Term - First Register (Logic Var 0 to 15)
BM(16)
Bit 15 - 50TQ picked-up
Bit 14 - 150T neutral picked-up
Bit 13 - 50T neutral picked-up
Bit 12 - 150T phase picked-up
Bit 11 - 50T phase picked-up
Bit 10 - 51Q tripped
Bit 9 - 151 neutral tripped
Bit 8 - 51 neutral tripped
Bit 7 - 151 phase tripped
Bit 6 - 51 phase tripped
Bit 5 - 150TQ tripped
Bit 4 - 50TQ tripped
Bit 3 - 150T neutral tripped
Bit 2 - 50T neutral tripped
Bit 1 - 150T phase tripped
Bit 0 - 50T phase tripped
Mask and Term - Second Register (Logic Var 16 to 31)
BM(16)
Bit 15 - Logic always false
Bit 14 – Spare
Bit 13 - 79SCB
Bit 12 - 79RST
Bit 11 - 79LO
Bit 10 - 79RNG
Bit 9 - 79C
Bit 8 – 79P
Bit 7 – 143 Switch
Bit 6 – 43 Switch
Bit 5 - 51Q picked-up
Bit 4 - 151N picked-up
Bit 3 - 51N picked-up
Bit 2 - 151 phase picked-up
Bit 1 - 51 phase picked-up
Bit 0 -150TQ picked-up
Mask and Term - Third Register (Logic Var 32 to 47)
BM(16)
Bit 15 - Virtual Output 15 status
Bit 14 - Virtual Output 14 status
Bit 13 - Virtual Output 13 status
Bit 12 - Virtual Output 12 status
Bit 11 - Virtual Output 11 status
Bit 10 - Virtual Output 10 status