Technical data – BECKHOFF BC7300 User Manual

Page 14

Advertising
background image

Basic Principles

BC7300

14


Technical data

The MODBUS – the fieldbus-specific electrical data is listed in this section.
The following table gives an overview of all the data:

Technical data

BC7300

Supply voltage

24 V DC

Input current

70mA +
(total K-Bus current)/4
500 mA max.

Power-on surge

2.5 x steady operating current

K Bus supply current up to

1750 mA max.

Configuration facility

via KS2000 or the controller

Number of Bus Terminals

64

Digital peripheral signals

256 inputs/outputs

Analog peripheral signals

128 inputs/outputs

Baud rate

From 150 baud to 38400 baud

Protocol

RTU and ASCII

Bus connection

D-Sub RS 485
9-pin

Voltage

of

the

power contact

24 V DC / AC max.

Power

contacts

current

drawn

10 A max.

Electric strength

500 Veff (power contact / supply voltage / fieldbus)
none

Typical weight

170 g

Operating temperature

0°C ... +55°C

Storage temperature

-20°C ... +85°C

Relative humidity

95% without dew formation

Vibrations/Shock resistance conforms to IEC 68-2-6 / IEC 68-2-27
EMC resistance burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20

PLC data

Programmability via programming interface (TwinCAT BC/TwinCAT)

Program size approx. 3000 PLC statements

Program memory 32 kbytes / 96 kbytes

Data memory 32 kbytes / 64 kbytes

Remanent flags 512 bytes

Runtime system 1 PLC task

PLC cycle time approx. 3 ms for 1000 instructions (including K-Bus I/O cycle)

Programming languages IL, LD, FBD, SFC, ST

Station addresses selectable to 99 via DIP switch

0 Programming mode and configuration mode
1 – 99 Slave address

Baud rate in programming

mode

19,200 baud, 8 data bits, even parity, one stop bit


Current consumption on
the K-Bus

The Bus Terminals require energy for the operation of the K-Bus
electronics, and this is supplied by the Bus Coupler. Find the current
consumption of the K-Bus from the catalogue, or from the appropriate data
sheets for the Bus Terminals. Consider the maximum output current of the
Bus Coupler that is available for supply of the Bus Terminals. A special
power supply terminal (KL9400) can be inserted at any location to insert
more power into the K-Bus. Refer to Beckhoff’s technical support
department regarding the use of a power supply terminal.