BC7300

25


Parameterisation Table

Parameter

x 10

x 1

Default

Parameter value

0

1..9

-

Indicates the parameter of the x 10 function

1

RTU mode

Modbus 1

2

1

ASCII mode

1

8 data bits, no parity

one stop bit

2

8 data bits even Parity

one stop bit

3

8 data bits odd Parity

one stop bit

4

7 data bits even Parity

one stop bit

5

7 data bits odd Parity

one stop bit

6

one stop bit

7

2 stop bits

8

8 data bits, no parity

two stop bits

9

8 data bits even Parity

two stop bits

10

8 data bits odd Parity

two stop bits

11

7 data bits even Parity

two stop bits

Frame 2

12

1

7 data bits odd Parity

two stop bits

1

38400 baud

2

19200 baud

3

9600 baud

4

4800 baud

5

2400 baud

6

1200 baud

7

600 baud

8

300 baud

Baud rate 3

9

3

150 baud

End of Frame Time 4

0..9

0

In ms for RTU mode (0 dependent on the baud
rate)
In seconds for ASCII mode (0 EOF time switched
off)

Watchdog 100 ms 5

0..9

0

Watchdog x 100 ms

Watchdog 1000 ms 6

0..9

1

Watchdog x 1000 ms

Factory setting 9