MODBUS

34

BC7300


Query

Byte Name

Example

RTU

ASCII

Start frame

„:“

0x3A

Slave address 11

0x0B

„0B“

0x30, 0x42

Function code 23

0x17

„17“

0x31, 0x37

Read start address

high

0

0x00

„00“

0x30, 0x30

Read start address

low

0

0x00

„00“

0x30, 0x30

Read length high 0

0x00

„00“

0x30, 0x30

Read length low 2

0x02

„02“

0x30, 0x32

Write start address

high

8

0x08

„08“

0x30, 0x38

Write start address

low

0

0x00

„00“

0x30, 0x30

Write length high 0

0x00

„00“

0x30, 0x30

Write length low 2

0x02

„02“

0x30, 0x32

Byte Count 4

0x04

„04“

0x30, 0x34

Data 1 high 63

0x3F

„3F“

0x33, 0x46

Data1 low 255

0xFF

„FF“

0x46, 0x46

Data 2 high 127

0x7F

„7F“

0x37, 0x46

Data 2 low 255

0xFF

„FF“

0x46, 0x46

Error Check

LRC / CRC

0x76
0xD3

„12“

0x31, 0x32


End of frame

T1-t2-t3

CRLF

0xD, 0xA


Response

The Bus Terminal Controller replies with the start address and the length of
the bytes to be transferred in "Byte count". The data information follows. In
this example the first word contains 0x0038 (hex) while the second word
contains 0x3F0B.

Byte Name

Example

RTU

ASCII

Start frame

„:“

0x3A

Slave address 11

0x0B

„0B“

0x30, 0x42

Function code 23

0x17

„17“

0x31, 0x37

Byte Count 4

0x04

„04“

0x30, 0x34

Data 1 high 0

0x00

„00“

0x30, 0x30

Data 1 low 56

0x38

„38“

0x33, 0x38

Data 2 high 63

0x3F

„3F“

0x33, 0x46

Data 2 low 11

0x0B

„0B“

0x30, 0x42

Error Check

LRC / CRC

0x82
0xDD

„58“

0x35, 0x38


End of frame

t1-t2-t3

CRLF

0xD, 0xA


Diagnostics

In the MODBUS, function 08 provides a series of tests for examination of
the communication system between the master and the slave and for
inspection of a variety of internal error states within the slave. A broadcast
telegram is not supported.

The function uses a two-byte sub-function code field in the query to define
the test that is to be carried out. The slave outputs the function code and
the sub-function code as an answer.

The diagnostic queries use a two-byte data field to send diagnostics data
or control information to the slave.