23


Assignment of the Bus Terminals

In the default setting, all the Bus Terminals are assigned to the Bus
Terminal Controller. This can be changed with the KS2000 software. The
assignment of the terminals is specified in Table 1 of the BC7300.

Hex

Bin

Description

0

00

The Bus Terminal is assigned to the MODBUS, and byte-
oriented Bus Terminals are given compact mapping (user
data only)

1

01

No function

2

10

The Bus Terminal is assigned to the BC, and byte-oriented
Bus Terminals are given compact mapping (user data only)

3

11

The Bus Terminal is assigned to the BC, and byte-oriented
Bus Terminals are given complex mapping (with control
and status)

Compact

Compact evaluation of a byte-oriented Bus Terminal means that only the
user data is transmitted.
Example: a KL3xx2 has 2 input words, and a KL4xx2 has 2 output words.

Complex

Complex evaluation of a byte-oriented Bus Terminal means that the user
data and the control and status byte are transmitted.
Example: a KL3xx2 has 4 input words and 4 output words; the same
applies to a KL4xx2.
You will find further information in the documentation for the Bus
Terminals.

Table 1

Default

Description

Offset 4 0xFFFF

1.-8. terminal

Offset 5 0xFFFF

9.-16. terminal

Offset 6 0xFFFF

17.-24. terminal

Offset 7 0xFFFF

25.-32. terminal

Offset 8 0xFFFF

33.-40. terminal

Offset 9 0xFFFF

41.-48. terminal

Offset 10 0xFFFF

49.-56. terminal

Offset 11 0xFFFF

57.-64. terminal


KS2000 example

As from Version 2.3.2, the KS2000 software permits the adaptation of the
Bus Terminals to be set via a dialogue. You can update your KS2000
software at www.Beckhoff.de.