Technical / PLC Data

The electrical data of the RS485 bus terminal controller are presented in
this chapter. The bus terminal controller is set to 19,200 baud data rate.
Addresses from 0 to 99 are selectable via two address selectors on the
coupler. The following table gives an overview of all the data:

Technical data

BC8000

Number of bus terminals

64

Digital

peripheral signals

256 inputs and outputs

Analogue peripheral signals

128 inputs and outputs

Peripheral bytes

512 inputs and 512 outputs

Electrical power supply

24 V (- 15% / +20%) EN 61131

Input current

70 mA + (total K bus current)/4
500 mA max.

Power-on surge

2.5 x steady operating current

K-bus output current

1750 mA max.

Connector

1 x D-sub plug, 9-pin

Voltage of the power contact

24 V DC / AC

Power contacts current

drawn

10 A

Voltage stability

500 Veff (power contact / supply voltage)

Typical weight

170 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95% without dew formation

Vibration/shock stability

according to IEC 68-2-6 / IEC 68-2-27

EMC immunity, burst / ESD

according to EN 61000-4-4 / EN 61000-4-2, limit values in accordance with
EN 50082-2

Installation location

arbitrary

Protection class

IP20

PLC data

Programmability

via programming interface or RS485 interface (TwinCAT BC/TwinCAT)

Program size

approx. 3000 PLC statements

Program memory

32 kbytes / 96 kbytes

Data storage

32 kbytes / 64 kbytes

Remanent flags

512 bytes

Runtime system

1 PLC task

PLC cycle time

approx. 3 ms for 1000 instructions (including K-bus I/O cycle)

Programming languages

IL, LD, FBD, SFC, ST

Station addresses

Selectable to 99 via DIP switch
0: reserved
1 – 98: programming mode
99: interface available for the PLC program

Interface

RS485

Baud rate

19,200 baud, 8 data bits, even parity, one stop bit


Current consumption on the
K-bus

For operation of the K-bus electronics, the bus terminals require energy
from the K-bus that is supplied by the bus coupler. Refer to the catalog or
the corresponding data sheets of the bus terminals for details of the K-bus
current consumption. In doing so, pay attention to the maximum output
current of the bus coupler that is available for powering the bus terminals.
Using a special power supply terminal (KL9400), power can be fed back
into the K-bus at any chosen point. If you wish to use a power supply
terminal, please contact Beckhoff’s technical support.