Bc8000, 5 v 5: gnd 3: rxd/txd 8: rxd/txd – BECKHOFF BC8000 User Manual

Page 22

Advertising
background image

RS485 – Controller BC8000

22

BC8000

i

Note

When addresses 1..98 are selected the baud rate cannot be set. It is
identical to the default value.

Setting of station addresses Selection of station addresses is carried out using the rotary switches on the

left side of the bus terminal controller. The address is set as decimal
number. The upper rotary switch sets the units value and the low one the
tens value of the address. (Example: station address 18: lower rotary switch
= 1, upper rotary switch = 8). In order for the rotary switch setting to be
stored by the bus terminal controller, a reset of the bus terminal controller
must be carried out (brief interruption of the power supply or software reset).

Address selector


The Medium: Plugs and Cables

Cable connection is provided by a 9-pin D-sub plug on the left side of the
bus terminal controller. A two-conductor shielded cable can be used in which
the shield is bonded to the signal ground (GND).

1

6: 5 V

5: GND
3: RxD/TxD

8: RxD/TxD

With the BC8000 bus terminal controllers can connections be developed with
several participants, whereby the maximum length amounts to 1200m.

PC

TxD/RxD (3)
RxD/TxD (8)

BC8000

RxD/TxD (3)
TxD/RxD (8)

Shield

PE

Address

selector