Dataprobe iBoot-G2 Operation Manual User Manual

Page 27

Advertising
background image

V140506E

iBoot-G2+

Page 27

Device Commands

Set commands are available to the administrator only

set location <20 char. max>
get location

This command is used to set the iBoot-

G2’s location ID.

Get returns the current setting

New Boot

set cycle <1-999>
get cycle

This command sets the cycle time in seconds
Get returns the current setting

5

set delay <0-999>
get delay

This command sets the delay time in seconds
Get returns the current setting

1

set timeout <0-99>
get timeout

This command sets the auto logout time in minutes
Get returns the current setting

2

set <main |exp1 | exp2> initial state <on |
off | last>
get initial state

This command sets the initial state of the outlet when the
iBoot-G2 is initially powered up

Last

set upgrade enable <yes | no>

Enables or disables the ability to upload new firmware to
the iBoot-G2.

no

login

Prompts for admin credentials when logged in as user

logout

Terminates the session

reboot

This command reboots the iBoot-G2.

Graceful Shutdown Commands

Set commands are available to the administrator only

Get gsd

This command returns all the current settings for
Graceful Shutdown

set gsd <main | exp1 | exp2> enabled
<yes | no>

This command enables or disables the shutdown delay
process.

no

set gsd <main | exp1 | exp2> ipaddress
<dotted decimal>

This command is used to set IP address of the target
system for graceful shutdown.

set gsd <main | exp1 | exp2> username
<20 char. max>

This command sets username of the target system

set gsd <main | exp1 | exp2> password
<20 char. max>

This command sets the password of the target system

set gsd <main | exp1 | exp2>
shutdowndelay <0-999>

This command sets the shutdown delay in seconds

set gsd <main | exp1 | exp2> rebootdelay
<0-999>

This command sets the reboot delay in seconds


Advertising