Heartbeat Commands

These commands are only available to the administrator.

get heartbeat

This command displays the heartbeat settings

Status Trigger Count
Source: None OK 0
Frequency: 10
Fail Count: 3
Action: None
Outlet: Main

set heartbeat source <none | usb |
network>

This command sets the source for the heartbeat.
Either USB or Network

None

set heartbeat port <1-65535>

This command sets the port for the heartbeat protocol.
The heartbeat uses UDP and can be the same port
number as DxP, which is TCP

9100

set heartbeat frequency <1-999>

This command is used to set the frequency, in
seconds. How often the iBoot-G2+ expects the
heartbeat

10

set heartbeat failcount <1-999>

This command is used to set the number of
consecutive failures the heartbeat must detect before
the iBoot-G2+ considers the device to be failed.

3

set heartbeat action <none | on-latch | on-
follow | off-latch | off-follow | cycle>

This command is used to set the action that the iBoot-
G2+ will perform when the heartbeat detector triggers.

None

set heartbeat cycle <1-999>

This command sets the maximum number of power
cycles when the heartbeat triggers

1

set heartbeat outlet <main | exp1 | exp2>

This command sets the outlet that the heartbeat will
trigger.

Main

User Commands

These commands are only available to the administrator.

set user account <yes | no>

This command sets whether or not a user account is
used. If <n> only the administrator account is active

n

set login required <yes | no>

This command sets whether or not a login is required
for user level operation. A login is always required for
admin functions.

y

set password <user | admin> <old> <new>
<repeat>

This command is used to set the password of either
the user or administrator.

user
admin