Dataprobe iBoot-G2 Operation Manual User Manual
Page 30

V140506E
iBoot-G2+
Page 30
Autoping Commands
These commands require a reboot before they will take effect.
These commands are available to the administrator only.
get autoping
This command returns all of the AutoPing settings as shown below.
Autoping 1 A B Status Trigger Count
IP Address: 123.12.123.12 0.0.0.0 OK 0
Frequency: 1 10
Fail Count: 1 3
Logic: A And B
Action: None
Cycle: 1
Outlet: Main
Wait: 2
Autoping 2 Status Trigger Count
IP Address: 0.0.0.0 OK 0
Frequency: 10
Fail Count: 3
Action: None
Cycle: 1
Outlet: Exp1
Wait: 2
Autoping 3 Status Trigger Count
IP Address: 0.0.0.0 OK 0
Frequency: 10
Fail Count: 3
Action: None
Cycle: 1
Outlet: Exp2
Wait: 2
set autoping <1a | 1b | 2 | 3> ipaddress
<dotted decimal>
This command is used to set the IP address of
AutoPing 1 or AutoPing 2
0.0.0.0
set autoping <1a | 1b | 2 | 3> frequency
<1-999>
This command is used to set the frequency, in
seconds (how often the iBoot-G2+ sends the ping) for
each of the AutoPings.
10
set autoping <1a | 1b | 2 | 3> failcount <1-
999>
This command is used to set the number of
consecutive failures the AutoPings must detect before
the AutoPing considers the pinged device to be failed.
3
set autoping 1 logic <a | and | or>
Sets logic for AutoPing 1. A = A Only, and = A and B,
or = A or B.
A and B
Set autoping <1 | 2 | 3> outlet <main |
exp1 | exp2>
This command sets the outlet that the AutoPing will
trigger.
Main
set autoping <1 | 2 | 3> action <none | on-
latch | on-follow | off-latch | off-follow |
cycle>
This command is used to set the action that the iBoot-
G2+ will perform when the AutoPing triggers.
None
set autoping <1 | 2 | 3> cycle <0-999>
This command sets the maximum number of power
cycles when the AutoPing triggers. 0 = Unlimited
1
set autoping <1 | 2 | 3> wait <1-999>
This command sets the time, in seconds for the device
to respond to a ping.
2